140CPU31110
Mô tả
Mô tả
Product overview
-
Model: 140CPU31110
-
Brand: Schneider Electric
-
Type: Unity Processor Module for Modicon Quantum Platform
General Information
-
Platform: Modicon Quantum
-
Clock frequency: 66 MHz
-
Internal memory: 548 kB RAM
-
Bus current: 1800 mA
I/O Capabilities
-
Local discrete I/O: Unlimited (max 27 slots)
-
Remote discrete I/O: 31,744 inputs and 31,744 outputs via S908
-
Distributed discrete I/O: 8,000 inputs and 8,000 outputs per Modbus Plus network
-
Local analog I/O: Unlimited (max 27 slots)
-
Distributed analog I/O: 500 inputs and 500 outputs per Modbus Plus network
-
Remote analog I/O: 1,984 inputs and 1,984 outputs via S908
-
Application-specific I/O: Includes high-speed interrupt, counter, accurate time stamping, serial link
Communication & Connectivity
-
Integrated ports:
– 1 Modbus Plus
– 2 Modbus RS232/485 -
Optional module support:
– Ethernet
– Modbus
– Modbus Plus
– Profibus DP
– Sy/Max -
Max connections:
– 2 Ethernet TCP/IP (local)
– 2 Modbus Plus (local)
– 2 Modbus (RS232/485)
– 2 AS-Interface (distributed)
– 4 AS-Interface (remote)
– 2 Profibus DP (local) -
Connection types:
– 1 SUB-D 9 (Modbus Plus)
– 2 SUB-D 9 (Modbus)
Rack & Slot Support
-
Number of slots: 16 total
-
Rack configuration:
– 2 local racks
– 63 distributed I/O stations (Modbus Plus)
– 31 remote I/O stations (S908)
– 0 Ethernet remote I/O
Application & Performance
-
Application tasks:
– 1 cyclic/periodic master task
– 1 fast periodic task
– 16 timer interrupt tasks
– 64 I/O interrupt tasks
– 64 interrupt tasks -
Execution speed:
– 0.1–0.27 µs (floating/fixed-point)
– 0.12–0.585 µs (Boolean/word) -
Instruction throughput:
– 1.86 Kinst/ms (100% Boolean)
– 2.49 Kinst/ms (65% Boolean, 35% numerical) -
System overhead:
– 0.2 ms (fast task)
– 1 ms (master task)
Indicators & Diagnostics
-
RUN (green): CPU solving logic
-
READY (green): Passed diagnostics
-
Modbus/Modbus Plus Comm (green): Active communication
-
Memory port (orange): Write protection active
-
BAT LOW (red): Low or missing battery
-
ERROR A (red): Modbus Plus error
Configuration Features
-
Memory port switch: ON/OFF
-
Comm port switch: ASCII/RTU/Memory
Lợi ích sản phẩm
Lợi ích sản phẩm
- 100% sản phẩm chính hãng có sẵn với giao hàng nhanh. Tìm hiểu thêm...
- Chính sách đổi trả trong 30 ngày để đảm bảo chất lượng. Tìm hiểu thêm...
- Bảo hành 12 tháng để bạn yên tâm. Tìm hiểu thêm...
Đánh giá
Đánh giá
Chia sẻ thêm

Có câu hỏi?
Thông báo qua email khi sản phẩm này có sẵn
Sản phẩm được đề xuất
Sản phẩm đã xem gần đây
Đăng ký nhận email từ chúng tôi
Hãy là người đầu tiên biết về các bộ sưu tập mới và các ưu đãi độc quyền.