FBM207C
คำอธิบาย
คำอธิบาย
Product Overview
-
Model: FBM207C
-
Type: Contact Sense Input Interface Module
-
Communication: Via redundant 2 Mbps Fieldbus with FCM or FCP
Inputs & Accuracy
-
Channels: 16 isolated and independent
-
Pulse Count Accuracy: No missing pulses at 0–250 Hz
-
Filter/Debounce Time: Configurable (No filter, 4, 8, 16, or 32 ms)
Voltage Monitor Input
-
Logic One (On-State Voltage): 15 to 60 V DC
-
Logic Zero (Off-State Voltage): 0 to 5 V DC
-
Current: 1.4 mA typical at 5 to 60 V DC
-
Source Resistance Limits:
Logic One: max 1 kΩ at 15 V DC
Logic Zero: min 100 kΩ at 60 V DC
Contact Sensor Input
-
Voltage: 48 V DC ±15%
-
Short-Circuit Current: 3.2 mA typical
-
Logic One (On-State Resistance): max 1.0 kΩ
-
Logic Zero (Off-State Resistance): min 100 kΩ
Power Requirements
-
Input Voltage Range (Redundant): 24 V DC +5%, -10%
-
Power Consumption: 5 W
-
Heat Dissipation: 5 W
-
Loop Power Supply Protection: Current limited at 3.2 mA typical
Physical Dimensions & Weight
-
Height: 130 mm (5.12 in)
-
Width: 25 mm (0.98 in)
-
Depth: 150 mm (5.9 in) including baseplate connectors (139 mm / 5.46 in without)
-
Weight: 185 g (6.5 oz) approximate