YS1700-101/A34
Description
Description
The Yokogawa YS1700-101/A34 is a programmable indicating controller from the YS1000 series, designed for process measurement, indication and feedback control. It combines a hard manual operating unit with Ethernet communication using Modbus/TCP. The controller supports local operation and communication with host systems, allowing process variables, setpoints and control outputs to be exchanged with supervisory equipment.
Model Identification
The ordering code identifies the controller configuration:
- YS1700: Programmable indicating controller.
- -1: With hard manual unit.
- 0: Basic type.
- 1: 220 V AC power supply.
- /A34: Ethernet communication option using Modbus/TCP.
The /A34 option is specified for YS1700 suffix configurations with -x0x or -x1x, which includes the supplied -101 configuration.
Control and Indication Functions
The YS1700 supports programmable operation and function-selection modes. Its control functions include single-loop, cascade and selector control. Function-block programming allows users to configure signal processing, control calculations and I/O assignments according to the required control strategy.
The hard manual unit provides a separate manual output adjustment path. Yokogawa's design incorporates a hard manual circuit independent of the digital circuits, allowing manual adjustment of the controller output during failures involving the digital control circuitry.
I/O Configuration
The -101 configuration is the basic type without expandable I/O. Its standard I/O arrangement includes:
- 5 analog inputs: 1-5 V DC signals in programmable mode.
- 2 analog outputs: 1-5 V DC, with one output configurable for 4-20 mA DC.
- 6 shared digital I/O points: Each point can be assigned as a digital input or digital output through parameter settings.
The analog inputs receive process measurement signals, while the analog outputs transmit calculated control signals or other assigned variables. Digital I/O points handle discrete status, command and control functions.
Ethernet Communication
The /A34 option provides an Ethernet interface supporting Modbus/TCP in server mode. The physical connection uses a rear-mounted RJ45 connector and supports 10BASE-T and 100BASE-TX Ethernet.
- Maximum number of Ethernet connections: 2.
- Maximum cable segment length: 100 m.
- Protocol: Modbus/TCP (Server).
- Maximum transactions: 1 per connection.
The interface allows a host system to read controller measurements and access supported parameters. Write access to parameters can be disabled. The controller also provides configurable behavior following a sustained communication failure, with MAN or AUT available as the selected fallback mode.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | YS1700-101/A34 |
| Brand | Yokogawa |
| Product Type | Programmable Indicating Controller |
| Series | YS1000 |
| Controller Type | Basic Type |
| Manual Operation | Hard manual unit |
| Power Supply | 220-240 V AC, 50/60 Hz |
| Maximum Power Consumption | 30 VA |
| Analog Inputs | 5 x 1-5 V DC |
| Analog Outputs | 2 x 1-5 V DC; one configurable for 4-20 mA DC |
| Digital I/O | 6 configurable DI/DO points |
| Communication Interface | Ethernet, RJ45 |
| Communication Protocol | Modbus/TCP (Server) |
| Ethernet Standard | 10BASE-T/100BASE-TX |
| Ethernet Connections | 2 maximum |
| Analog I/O Conversion Accuracy | +/-0.1% of span for 1-5 V inputs and main-unit voltage outputs |
| Operating Temperature | 0 to 50 deg C |
| Operating Humidity | 5 to 90% RH, non-condensing |
| Front Panel Protection | IP54 |
| Mounting | Indoor panel mounting |
| Dimensions (H x W x D) | 144 x 72 x 250 mm |
| Panel Cutout | 137 x 68 mm |
| Weight | 1.6 kg |
Installation and Configuration Notes
The controller is designed for indoor panel mounting using upper and lower mounting brackets. The specified panel thickness is 2.3 to 25 mm. Allow at least 100 mm clearance above and below the instrument for ventilation.
The IP54 protection rating applies to the front panel and is not applicable to side-by-side multi-unit installation. The rear wiring connections use M4 screw terminals.
Frequently Asked Questions
Q: What is the difference between YS1700-101/A34 and a YS1700 without Ethernet?
A: The /A34 suffix identifies the Ethernet communication option, which provides Modbus/TCP server communication through the rear RJ45 connector. This option is part of the original ordering configuration and cannot simply be added as a field retrofit.
Q: Can the hard manual unit operate during a digital circuit failure?
A: Yes. The hard manual circuit operates independently of the digital circuits and allows manual adjustment of the controller output during a digital circuit failure, including failures involving both CPUs.
Q: Can the YS1700-101/A34 use expandable I/O?
A: No. The -101 configuration identifies the basic type, not the basic type with expandable I/O. The expandable I/O configuration uses the -x1x suffix arrangement, whereas this model uses -x0x.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.