YNT511D-V42/KT
Description
Description
The Yokogawa YNT511D-V42/KT is an optical bus repeater for Yokogawa's V net communication system. It uses fiber-optic transmission to extend communication distances between network segments while maintaining the dual-redundant bus configuration. The YNT511D model supports transmission distances of up to 4 km per optical repeater pair, subject to the specified fiber type, optical loss, and overall network configuration.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | YNT511D-V42/KT |
| Brand | Yokogawa |
| Product Type | Optical Bus Repeater |
| Network | V net |
| Bus Configuration | Dual-redundant |
| Transmission Medium | Fiber-optic cable |
| Maximum Transmission Distance | 4 km per optical repeater pair |
| Power Supply | 24 V DC, indicated by the model's 4 power-supply code |
| Option Code | /KT |
Network Function and Transmission Limits
The YNT511D converts the electrical V net communication path to an optical-fiber link, allowing the network to span distances beyond those supported by a single coaxial cable segment. It is intended for V net rather than standard Ethernet, even though Yokogawa documentation uses 10BASE-2 and 10BASE-5 terminology to describe the cable configurations.
The 4 km transmission rating applies to a pair of YNT511D optical bus repeaters. Actual network reach also depends on fiber specifications, optical attenuation, repeater count, and the total transmission-distance restrictions of the V net system.
Frequently Asked Questions
Q: Can one YNT511D repeater provide a 4 km optical link?
A: The documented 4 km configuration uses two YNT511D optical bus repeaters, one at each end of the optical link. The fiber type and optical-loss budget must meet the manufacturer's specifications.
Q: Is the YNT511D-V42/KT compatible with standard Ethernet networks?
A: No. The YNT511D is designed for Yokogawa V net communication. The 10BASE-2 and 10BASE-5 references in its documentation describe cable configurations and do not mean that V net is standard Ethernet.
Q: What should be checked when replacing an existing YNT511D?
A: Verify the complete model code, power-supply configuration, /KT option, fiber interface requirements, and existing V net topology. The repeater must match the intended dual-redundant network configuration.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...