Skip to product information
1 of 3

SSC50D-F2524

Brand: Yokogawa
Order Number: SSC50D-F2524
Type: Duplexed Safety Control Unit
Country:
Low stock: 15 left

Description

Caret Down

The Yokogawa SSC50D-F2524 is a duplexed Safety Control Unit for the ProSafe-RS Safety Instrumented System (SIS), using Vnet/IP communication. It provides redundant processor and power supply configurations for safety logic execution. The F-type configuration supports an extended ambient temperature range and includes a fan unit. Its ordering code specifies a 220-240 V AC power supply and no explosion protection.

Functional Description

The SSC50D-F2524 serves as the control hardware in a ProSafe-RS Safety Control Station (SCS). Its duplexed architecture uses two processor modules to execute safety control functions, with redundant Vnet/IP and ESB bus interfaces for communication with the control network and connected safety node units.

The unit supports up to eight I/O modules per safety control unit and up to nine connected safety node units. The ESB bus provides the communication path between the control unit and distributed safety node hardware.

Technical Specifications

Parameter Specification
Model SSC50D-F2524
Brand Yokogawa
Product Type Duplexed Safety Control Unit
System Platform ProSafe-RS
Network Interface Dual-redundant Vnet/IP
ESB Bus Interface Dual-redundant
Processor MIPS R5000
Main Memory 32 MB
Vnet/IP Communication Speed 100 Mbps, full duplex
Network Interface Standard 100BASE-TX
Network Connector RJ45
Network Cable UTP, CAT5e or higher
Maximum Network Distance 100 m to Layer 2 switch
Power Supply Dual-redundant
Rated Input Voltage 220-240 V AC
Input Frequency 50/60 Hz
Power Consumption 290 VA
Operating Temperature -20 to 70 deg C
I/O Module Capacity Up to 8 per control unit
Safety Node Capacity Up to 9 per control unit
Weight 13 kg

Model Code Identification

The ordering code identifies the hardware configuration as follows:

Code Description
SSC50D Duplexed Safety Control Unit
-F Wide-range temperature type, -20 to 70 deg C, with fan unit
2 Dual-redundant power supply
5 Without explosion protection
2 220-240 V AC power supply
4 Without Safety Control Function License (R4.01.31 or later)

The final code 4 is a software licensing configuration, not a power supply specification. For R4.01.31 and later, the required patch software must be applied.

Installation and Configuration Notes

The SSC50D-F uses a fan unit for operation above 40 deg C ambient temperature. The wide-temperature configuration requires twelve M5 rack-mounting screws. Power supply and grounding connections use M4 screws.

The manufacturer's hardware specification also identifies SEC401 ESB bus coupler modules for installation in the seventh and eighth slots when connecting safety node units.

Frequently Asked Questions

Q: Does the SSC50D-F2524 include a Safety Control Function License?

A: No. The final suffix 4 identifies the configuration without the Safety Control Function License for R4.01.31 or later. The required software license must be specified separately.

Q: What is the difference between SSC50D-F2524 and the standard-temperature configuration?

A: The F configuration supports an ambient temperature range of -20 to 70 deg C and includes a fan unit. The standard S configuration supports -20 to 40 deg C.

Q: Does the SSC50D-F2524 support explosion-protected installations?

A: The suffix 5 specifies a configuration without explosion protection. It should not be treated as an explosion-protected model. Cabinet and installation requirements must follow the applicable ProSafe-RS installation guidance. 