Skip to product information
1 of 3

SNT501-13

Brand: Yokogawa
Order Number: SNT501-13
Type: Optical ESB Bus Repeater Module
Country:
Low stock: 15 left

Description

Caret Down

The Yokogawa SNT501-13 is an Optical ESB Bus Repeater Slave Module for Yokogawa safety control systems. It converts the ESB bus communication path to an optical link and provides the slave-side interface back to the ESB bus. The module supports star and chain connection methods, with up to two repeater stages and a standard total transmission distance of up to 5 km.

Optical ESB Bus Function

SNT501 operates on the slave side of an optical ESB bus connection. It receives the optical transmission from an SNT401 Optical ESB Bus Repeater Master Module or an N-ESB Bus Module, then connects through ESB bus cable to the SSB401 ESB Bus Interface Module on the safety node unit. This arrangement allows the ESB communication path to cross a fiber-optic section rather than relying entirely on copper bus cabling.

Network Configuration

The repeater supports both star and chain connection methods. Up to two connecting stages can be used. For the SNT401/SNT501 combination, the specified transmission distance is up to 5 km for two stages in the applicable configuration; Yokogawa documentation also specifies up to 10 km for Vnet/IP systems with R1.03 or later under the stated two-stage condition. 

Technical Specifications

Parameter Specification
Model SNT501-13
Brand Yokogawa
Product Type Optical ESB Bus Repeater Slave Module
Function ESB Bus optical transport function
Connection Method Star type; Chain type
Number of Connecting Stages Maximum 2
Transmission Distance Maximum 5 km, total two stages
Extended Distance with Vnet/IP R1.03 or Later Maximum 10 km, total two stages
Current Consumption 0.5 A
Weight 0.3 kg

Fiber-Optic Communication

The SNT501 is used with the corresponding optical repeater arrangement to extend the ESB bus through fiber-optic cable. Yokogawa documentation specifies quartz singlemode fiber for the optical ESB repeater system, with the SNT401/SNT501 combination supporting a maximum fiber-optic cable length of 5 km. The optical connector is specified as Type LC in the installation documentation.

System Connection

The SNT501 is the slave-side counterpart to the SNT401 Optical ESB Bus Repeater Master Module. In a typical ESB optical link, the master-side equipment converts the electrical ESB bus signal to an optical transmission, while the SNT501 receives the fiber signal and returns it to the ESB bus connection at the slave-side node.

Frequently Asked Questions

Q: Is SNT501-13 a master or slave optical repeater?

A: SNT501 is the Optical ESB Bus Repeater Slave Module. The SNT401 is the corresponding master module used at the other end of the optical ESB link.

Q: What is the maximum transmission distance of the SNT501 system?

A: The standard SNT401/SNT501 arrangement supports up to 5 km over the specified optical link, with a maximum of two connecting stages. For Vnet/IP systems with R1.03 or later, Yokogawa specifies up to 10 km for two stages under the stated configuration.

Q: Can SNT501 be used in both star and chain configurations?

A: Yes. The specified connection methods include both star-type and chain-type connections, allowing the repeater to be incorporated into either topology where the system configuration permits it. 