Skip to product information
1 of 3

SNB10D-425/CU2T

Brand: Yokogawa
Order Number: SNB10D-425/CU2T
Type: Safety Node Unit
Country:
Low stock: 15 left

Description

Caret Down

The Yokogawa SNB10D-425/CU2T is a rack-mountable Safety Node Unit designed for Yokogawa's ProSafe-RS safety instrumented system. It provides the interface between field I/O modules and the safety control unit through the ESB bus. This configuration includes dual-redundant power supplies, a 220-240 V AC power input, and an ESB bus connector unit with an integrated terminator.

Functional Description

The SNB10D provides the node-level interface for distributed safety I/O. It accommodates I/O modules and transfers their signals to the safety control unit through the ESB bus. The node also distributes power to the installed I/O modules.

The /CU2T option identifies a connector unit with an ESB bus terminator. It is intended for an end node in the ESB bus connection, distinguishing it from the /CU2N version, which uses a connector unit without the terminator.

Model Configuration

The complete ordering code identifies the following hardware configuration:

  • -4: Dual-redundant power supply configuration, for ProSafe-RS R4.01 or later.
  • 2: 220 to 240 V AC power supply, 50/60 Hz.
  • 5: ISA Standard G3 and operating temperature specification of -20 to 70 deg C, without explosion protection.
  • /CU2T: ESB bus connector unit with terminator, part number S9343FA.

The /CU2T configuration is relevant when selecting the node position in the ESB bus arrangement. The terminator distinguishes this version from the /CU2N configuration.

Technical Specifications

Parameter Specification
Model SNB10D-425/CU2T
Brand Yokogawa
Product Type Safety Node Unit
System ProSafe-RS
Mounting Type Rack Mountable
Power Supply Configuration Dual-redundant
Power Supply Voltage 220 to 240 V AC
Frequency 50/60 Hz
Power Consumption 230 VA
ESB Bus Connector S9343FA
ESB Bus Termination Integrated terminator
Operating Temperature -20 to 70 deg C
Environmental Classification ISA Standard G3
Explosion Protection Without explosion protection
Dimensions (H x W x D) 482.6 x 37.75 x 205 mm
Weight 5.9 kg
Mounting Fixings Four M5 screws
Standard Accessories 4 insulating bushes, S9049PM

Source: Yokogawa General Specifications GS 32Q06K10-31E.

ESB Bus and I/O Configuration

The SNB10D accommodates two power supply modules and two ESB bus interface modules (SSB401). The power supply modules provide power to the installed I/O modules, while the ESB interface modules handle communication with the safety control unit.

The maximum number of connectable safety nodes depends on the ESB bus coupler:

  • Up to 13 safety node units with the SEC402 ESB bus coupler on S2SC70S, S2SC70D, SSC60S or SSC60D safety control units.
  • Up to 9 safety node units with the SEC401 ESB bus coupler.

These limits apply to the specified system configurations and should be checked against the installed safety controller and bus coupler.

Installation and Connection Requirements

The SNB10D is designed for 19-inch rack mounting and is secured with four M5 screws. The supplied insulating bushes are used during mounting.

For connection to the safety control unit, Yokogawa specifies a YCB301 ESB bus cable with a minimum length of 1 m. The rack-mountable equipment must be installed in a keyed metallic cabinet to meet the applicable safety and EMC installation requirements.

Frequently Asked Questions

Q: What is the difference between SNB10D-425/CU2T and SNB10D-425/CU2N?

A: Both use the same SNB10D node configuration. The /CU2T version includes an ESB bus connector unit with a terminator, while /CU2N uses a connector unit without a terminator. The correct version depends on the node's position in the ESB bus arrangement.

Q: Does SNB10D-425/CU2T support redundant power supplies?

A: Yes. The -4 suffix specifies a dual-redundant power supply configuration for ProSafe-RS R4.01 or later. The node configuration includes two power supply modules.

Q: Can all I/O module slots be populated freely?

A: No. Yokogawa specifies restrictions on I/O module quantities and slot positions. Unused I/O module slots must be fitted with SDCV01 dummy covers. The applicable I/O module mounting requirements should be checked before configuring the node. 


Product Benefits

Caret Down

Reviews

Caret Down

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)
View full details

Recommended products

Recently viewed product