Description
Description
The Yokogawa SED2D-11 is a digital terminal board designed for single or dual-redundant digital I/O configurations in the ProSafe-RS system. It provides field wiring termination through M4 screw terminals and interfaces with the SDV521 digital I/O module through an AKB651 connection cable. Its four-channel-by-four arrangement supports organized termination of digital signal circuits.
Functional Description
The SED2D terminal board provides the physical connection between field wiring and the associated digital I/O module. It organizes field signal connections into four groups, each serving four channels, for a total arrangement of 16 channel connections.
For the documented ProSafe-RS configuration, the SED2D connects to the SDV521 through an AKB651 cable. The terminal board handles field-side wiring, while the connected I/O module performs the digital signal processing.
Redundant Configuration
The SED2D supports both single and dual-redundant configurations. When the I/O module is duplexed, the corresponding connector pairs must be used: CN1 and CN2, CN3 and CN4, CN5 and CN6, or CN7 and CN8.
This connector arrangement provides the wiring interface for redundant I/O connections. The installation must follow the designated connector pairing rather than using only one connector from a pair.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | SED2D-11 |
| Brand | Yokogawa |
| Product Type | Digital Terminal Board |
| System | ProSafe-RS |
| Configuration | Single or dual-redundant |
| Connection Points | 4 channels x 4 |
| Compatible I/O Module | SDV521 |
| Connection Cable | AKB651 |
| Terminal Type | M4 screw |
| Withstand Voltage | 2000 V AC for 1 minute |
| Insulation Resistance | 100 MOhm minimum at 500 V DC |
| Weight | 2.3 kg |
Electrical Isolation and Wiring
The specified withstand voltage of 2000 V AC for one minute is measured between the input signal terminals and the board case. The minimum insulation resistance of 100 MOhm is measured at 500 V DC. These values describe the board's electrical insulation characteristics and should not be confused with the operating voltage of the connected digital output circuits.
For field wiring, the M4 screw terminals provide mechanical connections for crimping terminals. Yokogawa's connection guidance specifies a recommended conductor cross-section of 0.5 mm2 to 2 mm2 (AWG 20 to 14) for M4 crimping terminals.
Frequently Asked Questions
Q: Which digital I/O module is specified for the SED2D terminal board?
A: The documented ProSafe-RS configuration pairs the SED2D with the SDV521 digital output module using the AKB651 dedicated signal cable. This combination is specified for 4-channel digital output applications.
Q: Can the SED2D be used in a dual-redundant configuration?
A: Yes. The SED2D supports single and dual-redundant configurations. For duplexed I/O connections, use the designated connector pairs CN1/CN2, CN3/CN4, CN5/CN6 or CN7/CN8.
Q: What should be checked when replacing an existing SED2D-11?
A: Check the complete model designation, terminal board configuration, connected SDV521 module and AKB651 cable arrangement. Also verify the existing redundant wiring and field terminal connections before replacement.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.