Skip to product information
1 of 3

SARM55W

Brand: Yokogawa
Order Number: SARM55W
Type: Mechanical Relay Board
Country:
Low stock: 15 left

Description

Caret Down

The Yokogawa SARM55W is a 32-point mechanical relay board designed for wet contact digital output applications in Yokogawa process control systems. It provides the field-side relay interface for digital output modules, allowing external devices to be switched using separately supplied field power. The board supports single or dual-redundant configurations and uses M4 screw terminals for field wiring.

Technical Specifications

Parameter Specification
Model SARM55W
Brand Yokogawa
Product Type Mechanical Relay Board
Output Type Wet Contact Relay Output
Output Points 32
Field Terminals M4 screw terminals
Maximum Load 250 V AC, 0.6 A per point
Maximum Load 30 V DC, 0.6 A per point
Maximum Load 125 V DC, 0.1 A per point
Minimum Load 5 V, 10 mA
Internal Circuit Supply 24 V DC, maximum 0.65 A
Field Power Supply Dual-line, one supply group per 16 points
Insulation Resistance At least 10 MOhm at 500 V DC
Withstanding Voltage 2 kV between field terminals and case
Withstanding Voltage 500 V between 24 V power terminals and case
Withstanding Voltage 2 kV between 24 V power terminals and field terminals
Operating Temperature 0 to 50 deg C
Relative Humidity 10 to 90% RH
Weight 2.2 kg

Output Configuration and Function

The SARM55W uses mechanical relays to convert digital output commands from the control system into wet contact switching signals for field devices. Unlike a dry-contact board, it receives external field power and supplies powered contact outputs to connected loads.

The 32 output points are divided into two groups:

  • Channels 1-16: First field power supply group.
  • Channels 17-32: Second field power supply group.

Each group has a separate field power supply connection. The internal relay circuit requires an independent 24 V DC supply, separate from the field-device power supply.

Module and Cable Compatibility

The Yokogawa specification identifies the following connections for the ARM55W relay board:

Component Compatible Model
32-point Digital Output Module ADV551
64-point Digital Output Module ADV561
Terminal Block ATD5A (with ADV551)
32-point Signal Cable AKB331
64-point Signal Cable AKB337

For an ADV561 64-point configuration, two relay boards and two AKB337 signal cables are required. The ADV551 configuration uses one 32-point relay board and the ATD5A terminal block.

Field Wiring and Load Requirements

The M4 screw terminals provide the field-device connections. The maximum switching load depends on the voltage type, so the connected load must remain within the corresponding AC or DC rating.

For inductive loads, Yokogawa specifies an external noise protection circuit connected in parallel with the load:

  • AC loads: RC protection circuit.
  • DC loads: Diode protection circuit.

These measures help suppress switching transients that can affect relay contacts and connected circuits.

Frequently Asked Questions

Q: What is the difference between ARM55W and ARM55D?

A: ARM55W provides wet contact outputs with an external field power supply. ARM55D provides dry contact outputs without the field power supply arrangement. Their maximum contact load ratings also differ.

Q: Can the board be used with the ADV561 digital output module?

A: Yes. The documented 64-point configuration requires two ARM55W boards and two AKB337 signal cables.

Q: Does the board require an external power supply?

A: Yes. The internal relay circuit requires 24 V DC, with a maximum current consumption of 0.65 A. Separate field power supplies are also required for the two 16-point output groups.