SARM55C
Description
Description
The Yokogawa SARM55C, corresponding to the ARM55C mechanical relay board designation, provides 32-point dry-contact switching for digital output signals in the Yokogawa CENTUM VP Field Control I/O (FIO) subsystem. It interfaces ADV551 or ADV561 digital output modules with field devices, supporting normally open (NO) or normally closed (NC) contact configurations.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | SARM55C |
| Base Model | ARM55C |
| Brand | Yokogawa |
| Product Type | Mechanical Relay Output Board |
| Weight | 2.2 kg |
| Dimensions | 482.6 mm (W) x 132.5 mm (H), 3U |
| Operating Temp | 0 to 50 deg C |
| Relative Humidity | 10 to 90% RH |
| Power Consumption | 24 VDC, max. 0.85 A |
| Relay Points | 32 points |
| Output Type | Mechanical relay dry-contact output |
| Contact Configuration | NO or NC, selectable |
| Maximum Load | 30 VDC, 1.5 A per point |
| Minimum Load | 5 V, 10 mA |
| Compatible Modules | ADV551, ADV561 |
| Terminal Block | ATD5A (for ADV551 configuration) |
| Signal Cables | AKB331 (32-point), AKB337 (64-point) |
| Field Terminals | M3.5 screws; M4 for power input |
| Insulation Resistance | At least 10 Mohm at 500 VDC |
| Withstand Voltage | 2 kV AC (field terminals to case); 500 V AC (power terminals to case); 2 kV AC (field terminals to power terminals) |
Specifications are based on Yokogawa's FIO relay board documentation for ARM55C. The SARM55C designation is used in supplier listings; confirm the physical nameplate when matching replacement hardware.
Mechanical Relay Switching and Electrical Isolation
The SARM55C uses mechanical relay contacts to convert digital output commands from the ADV551 or ADV561 module into field-side dry-contact switching signals.
Each of the 32 channels operates through an individual relay contact. The output can be configured as an a-contact (NO) or b-contact (NC), depending on the required field circuit arrangement.
The board uses a separate 24 VDC supply for its internal relay circuitry, with a maximum current consumption of 0.85 A. This supply is distinct from the external field load circuit.
Electrical isolation specifications include:
- Minimum insulation resistance of 10 Mohm at 500 VDC.
- 2 kV AC withstand voltage between field terminals and the case.
- 500 V AC withstand voltage between 24 V power terminals and the case.
- 2 kV AC withstand voltage between field terminals and 24 V power terminals.
For inductive loads, Yokogawa specifies an RC protection circuit for AC loads or a diode for DC loads connected in parallel with the load. This limits switching noise generated by inductive energy during relay contact operation.
Frequently Asked Questions (FAQ)
Q: Can the SARM55C operate with both ADV551 and ADV561 digital output modules?
A: Yes. The ARM55C relay board is specified for both ADV551 (32-point DO) and ADV561 (64-point DO) configurations. The ADV551 configuration uses the ATD5A terminal block. The ADV561 configuration requires two relay boards and two AKB337 signal cables.
Q: Does the SARM55C support normally open and normally closed outputs?
A: Yes. Each relay output can be configured as an a-contact (NO) or b-contact (NC). The required contact arrangement must be selected according to the field wiring design.
Q: What electrical protection is required when connecting inductive loads?
A: For AC inductive loads, connect an RC protection circuit in parallel with the load. For DC inductive loads, use a diode protection circuit. Observe the specified maximum contact load of 30 VDC and 1.5 A per point.
Field Installation Guidelines
1. Mounting: Install the relay board in the designated FIO cabinet or rack position. Verify the 3U mounting space and mechanical fixing points.
2. Signal Connections: Use the specified AKB331 or AKB337 signal cable according to the connected digital output module configuration.
3. Power Wiring: Connect the external 24 VDC supply for the internal relay circuit. Verify polarity and supply capacity before energizing.
4. Field Terminations: Use the specified M3.5 screw terminals for field connections and M4 terminals for the power input section. Ensure correct crimp terminal dimensions.
5. Load Protection: Install suitable suppression components across inductive loads to reduce switching transients and contact interference.
6. Electrical Inspection: Check terminal tightness, insulation condition, contact configuration and field wiring continuity before commissioning.
7. Functional Testing: Test each output channel against the corresponding ADV551 or ADV561 command and verify the expected NO/NC contact behavior.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.