Description

Caret Down

The Yokogawa SARM15A, also identified with the ARM15A mechanical relay contact input board designation, provides a 32-point interface for acquiring dry-contact signals in the Yokogawa CENTUM VP Field Control Unit (FIO) subsystem. It connects field contact devices to ADV-series digital input modules through mechanical relay circuits, with M4 screw terminals and external 24 V DC power distribution.

Hardware Specifications

Parameter Specification
Model SARM15A
Related Hardware Designation ARM15A
Brand Yokogawa
Product Type Mechanical Relay Contact Input Board
System CENTUM VP FIO
Origin Japan
Weight 2.2 kg
Operating Temp 0 to 50 deg C
Operating Humidity 10 to 90% RH
Power Consumption 24 V DC, maximum 0.32 A (internal circuit)
Contact Input Points 32 points
Input ON Threshold 150 ohms or less
Input OFF Threshold 200 kohms or greater
Field Contact Minimum Load 24 V DC, 13 mA
Field Power Supply Dual-line 24 V DC, maximum 0.3 A per line
Field Terminals M4 screw terminals
Compatible DI Modules ADV151 (32-point), ADV161 (64-point)
Signal Cable AKB331 (32-point), AKB337 (64-point)
Insulation Resistance At least 10 Mohms at 500 V DC
Withstand Voltage 1.5 kV between field terminals and case; 500 V between power terminals and case; 1.5 kV between power and field terminals

tek-international.com+2

Mechanical Relay Contact Interface and Power Distribution

The SARM15A uses mechanical relay contacts to interface field-side dry-contact signals with the CENTUM VP digital input subsystem. The input state is determined by contact resistance: 150 ohms or less represents the ON condition, while 200 kohms or greater represents the OFF condition.

Its 32 input points are arranged with dual-line field power distribution, supplying 24 V DC to each group of 16 points. Each line supports a maximum current of 0.3 A. The internal circuit requires a separate 24 V DC supply with a maximum current consumption of 0.32 A.

The electrical isolation specifications define the separation between field terminals, power terminals, and the board enclosure. These ratings should be considered when checking grounding arrangements and field wiring insulation.

tek-international.com+1

Frequently Asked Questions (FAQ)

Q: Can the SARM15A operate with redundant digital input modules?

A: Yes. It supports single and dual-redundant configurations. For an ADV161 64-point input module, two ARM15A relay boards and two AKB337 signal cables are required.

Q: What is the electrical input threshold for detecting contact states?

A: The ON state requires a contact resistance of 150 ohms or less. The OFF state requires at least 200 kohms. Field contact ratings must satisfy the specified minimum load of 24 V DC at 13 mA.

Q: Does the SARM15A support hot-swapping?

A: Hot-swapping capability is not established by the available technical specifications. Isolate the relevant power supplies and follow the Yokogawa system maintenance procedure before removing or replacing the board.

tek-international.com+1

Field Installation Guidelines

  1. Rack Mounting: Install the board in the designated 19-inch rack position, allowing sufficient clearance for cable routing and maintenance access.
  2. Signal Wiring: Connect field dry-contact signals to the M4 screw terminals. Check terminal assignments against the Yokogawa connection diagram.
  3. Power Distribution: Provide the specified external 24 V DC supply for the internal circuit and separate field power connections. Observe the maximum current rating of each supply line.
  4. Signal Cable Connection: Use AKB331 for the 32-point ADV151 configuration. For ADV161 applications, verify the required dual-board and AKB337 cable arrangement.
  5. Grounding and Shielding: Connect the board chassis to the designated cabinet grounding system. Terminate cable shields according to the system grounding design to avoid unintended ground loops.
  6. Electrical Verification: Check field contact resistance, supply polarity, terminal tightness, and insulation before energizing the system.
  7. Commissioning: Verify all 32 input states through the connected digital input module and confirm correct signal transitions from the field devices.