SAI533-H53/A4D00
Description
Description
The Yokogawa SAI533-H53/A4D00 is an 8-channel analog output module that generates 4-20 mA DC signals for field devices. It provides module-level isolation and HART communication for supported field instrument diagnostics and configuration. The /A4D00 option specifies a dual-redundant pressure clamp terminal block, model STA4D-00, for analog signal connections. The module's suffix codes also specify its connection arrangement, environmental classification, and operating temperature range.
Key Functions
- Analog current output: Provides eight 4-20 mA output channels for transmitting control signals to compatible field devices.
- HART communication: Supports digital communication with compatible HART instruments over the analog signal loop, allowing access to supported device information.
- Module isolation: Provides isolation between the module's output circuitry and the system, as specified for this product family.
- Dual-redundant terminal configuration: The /A4D00 option identifies the dual-redundant pressure clamp terminal block. The complete redundant configuration requires an additional module with the same specifications but without the terminal-block option code.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | SAI533-H53/A4D00 |
| Brand | Yokogawa |
| Product Type | Analog Output Module (Current Output) |
| Output Channels | 8 |
| Rated Output Range | 4-20 mA |
| Output Range | 1.25-23 mA |
| Allowable Load Resistance | 230-600 ohm at rated output range |
| Rated Accuracy | +/- 48 uA |
| Data Update Frequency | 40 ms |
| Temperature Drift | +/- 16 uA per 10 deg C |
| Module Isolation | Yes |
| HART Communication | Supported |
| Withstand Voltage | 1.5 kV AC between output signal and system for 1 minute |
| Maximum Current Consumption | 320 mA at 5 V DC; 300 mA at 24 V DC |
| Terminal Block | Dual-redundant pressure clamp terminal block |
| Terminal Block Model | STA4D-00 |
| Operating Temperature | -20 to 70 deg C |
| Environmental Classification | ISA Standard G3 |
| Weight | 0.26 kg |
Specifications are based on Yokogawa's SAI533 module documentation. The listed weight applies to the pressure clamp terminal block or MIL cable configuration; the separately listed signal cable interface adapter configuration weighs approximately 0.33 kg.
Model and Suffix Identification
| Code | Specification |
|---|---|
| SAI533 | Analog output module, 4-20 mA, 8 channels, module isolation |
| -H | HART communication |
| 5 | For pressure clamp terminal block or MIL cable, without explosion protection |
| 3 | ISA Standard G3 and operating temperature of -20 to 70 deg C |
| /A4D00 | Dual-redundant pressure clamp terminal block for analog signals |
| STA4D-00 | Terminal block model associated with option /A4D00 |
The 5 suffix identifies a connection arrangement without explosion protection. Do not treat this configuration as suitable for hazardous locations requiring explosion-protected equipment unless the complete installation design and applicable approvals establish suitability.
HART Communication and Redundant Configuration
The HART-enabled SAI533 supports digital communication with compatible field instruments while retaining the 4-20 mA analog output. Yokogawa documents HART-based instrument management through Plant Resource Manager (PRM) in ProSafe-RS, including partial stroke testing for supported valve positioners equipped with the required PST function. Actual availability depends on the connected instrument and system configuration.
The /A4D00 terminal-block option is intended for use in a dual-redundant arrangement. According to Yokogawa's ordering guidance, this arrangement requires an additional SAI533 module with matching specifications but without the /A4D00 option code. The terminal-block option alone does not establish that a complete redundant system is installed or configured.
Frequently Asked Questions
Q: Is the SAI533-H53/A4D00 an analog input or analog output module?
A: It is an analog output module. It provides eight isolated 4-20 mA current output channels; it is not an analog input module.
Q: Does the SAI533-H53/A4D00 support HART communication?
A: Yes. The -H suffix identifies the HART communication function. HART device management and functions such as partial stroke testing require compatible field instruments and the appropriate ProSafe-RS and PRM configuration.
Q: Can the SAI533-H53/A4D00 be used in a dual-redundant configuration?
A: Yes. The /A4D00 option identifies the dual-redundant pressure clamp terminal block. Yokogawa specifies an additional module with matching specifications but without the terminal-block option code for the redundant arrangement.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...