NFDV561-P50
Description
Description
The Yokogawa NFDV561-P50 is a 64-channel isolated digital output module for the STARDOM FCN/FCJ autonomous controller platform. It provides 24 V DC transistor outputs in a current-sink configuration for switching external field loads. The module supports individual ON/OFF output control and configurable output fallback behavior, with an external field power supply required for output operation.
Functional Description
The NFDV561-P50 converts digital control commands from the FCN/FCJ controller into discrete electrical output signals. Its 64 output channels can control compatible DC field loads within the specified voltage and current limits.
The current-sink output arrangement switches the load current toward the common negative supply. Field devices must therefore be wired with the correct polarity and an appropriate external 24 V DC supply.
Output Characteristics
The module provides isolated 24 V DC digital outputs, with a maximum load current of 100 mA per channel. The maximum output ON voltage drop is 2 V DC, while the maximum leakage current in the OFF state is 0.1 mA.
Output isolation is specified between the output signals and the system, as well as between channel groups. The common negative side is arranged in groups of 16 channels, which should be considered when planning field wiring and grounding.
Output Status and Fallback Behavior
The module supports ON/OFF status output and configurable fallback actions. These settings determine how the output channels respond when the controller system enters a fallback condition:
- HOLD: Maintains the existing output states.
- OFF: Turns all output channels OFF.
- NO: Performs no fallback action.
The selected fallback behavior should match the process requirements and the field device's response to loss of normal control.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | NFDV561-P50 |
| Brand | Yokogawa |
| Product Type | Digital Output Module |
| Controller Platform | STARDOM FCN/FCJ |
| Number of Output Channels | 64 |
| Rated Applied Voltage | 24 V DC |
| Load Voltage | 24 V DC, 100 mA |
| Field Power Supply Range | 20.4 to 26.4 V DC |
| Output Format | Current sink |
| Maximum Output ON Voltage | 2 V DC |
| Maximum OFF-State Leakage Current | 0.1 mA |
| Maximum Load Current | 100 mA/channel at 26.4 V |
| Output Response Time | 3 ms or less (status output) |
| Isolation Voltage | 2,000 V AC for 1 minute (output signal to system); 500 V AC for 1 minute (between commons) |
| Maximum Current Consumption | 780 mA at 5 V DC; 120 mA at 24 V DC field supply |
| Output Fallback | HOLD, OFF, NO |
| Fallback Detection Time | 4 seconds |
| External Connection | MIL connector cable |
| Weight | 0.3 kg |
Specifications are based on Yokogawa General Specifications GS 34P02Q35-01E.
Model Suffix Identification
The NFDV561-P50 ordering code identifies the module's output configuration and hardware version.
| Code | Description |
|---|---|
| NFDV561 | 64-channel, 24 V DC isolated digital output module |
| -P | Standard type |
| 5 | General-purpose type with no explosion protection |
| 0 | Basic type |
The P50 configuration does not include the ISA Standard G3 option. It should not be confused with the P51 configuration, which includes that option.
Installation and Wiring Considerations
The module requires an external 24 V DC field power supply. Its MIL connector cable interface must be considered when selecting the associated field wiring and terminal arrangement.
When driving DC relays, Yokogawa specifies connecting a diode. The common negative connections are grouped in blocks of 16 channels, so field wiring should account for these electrical grouping arrangements.
The fallback selection applies commonly to all output channels rather than allowing separate HOLD, OFF, or NO settings for individual channels.
Frequently Asked Questions
Q: Is the NFDV561-P50 a sourcing or sinking digital output module?
A: It uses a current-sink output configuration. Field loads must be connected with the appropriate external 24 V DC supply and polarity.
Q: What is the difference between NFDV561-P50 and NFDV561-P51?
A: The P50 version is the general-purpose configuration without explosion protection or the ISA Standard G3 option. The P51 version includes the ISA Standard G3 option. These configurations should not be treated as interchangeable without checking the applicable installation requirements.
Q: What happens to the outputs when a fallback condition occurs?
A: The module supports three fallback selections: HOLD maintains existing output states, OFF resets all output channels, and NO performs no fallback action. The detection time is 4 seconds, and one fallback selection applies to all channels.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.