NFBU200-S01
Description
Description
The Yokogawa NFBU200-S01 is a base module for the FCN (Field Control Node) controller platform. It provides the mounting structure and internal backplane connections for CPU, power supply, and I/O function modules. The NFBU200 long-type base module supports modular controller configurations, with dedicated power supply positions and function-module slots.
Functional Role in the FCN System
The base module acts as the mechanical and electrical foundation of the controller assembly. Its internal SB bus provides the connection between installed modules, allowing the CPU and I/O modules to operate as part of the same control unit.
The NFBU200 long-type platform has 10 module positions: two power supply slots and ten function-module positions in the overall slot arrangement. In a standard control-unit configuration, two positions are reserved for the CPU, leaving capacity for up to 8 I/O modules. Actual capacity changes with CPU and bus-repeater redundancy configurations.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | NFBU200-S01 |
| Brand | Yokogawa |
| Product Type | FCN Base Module (Long Type) |
| Controller Platform | FCN Autonomous Controller |
| Power Supply Slots | 2 |
| Function Module Slots | 10 |
| Maximum I/O Modules | 8 in a standard control-unit configuration |
| Internal Bus | SB bus |
| Mounting | NFBU200 supports 19-inch rack or DIN rail versions; exact S01 configuration requires confirmation |
| Weight | 1.9 kg |
| Dimensions | 482.6 x 132.5 x 40.5 mm |
| Maximum 5 V Self-Consumption | 0.4 A |
| 24 V Self-Consumption | 0 A |
Module Configuration and Redundancy
The two power supply positions allow a redundant power supply arrangement when the specified compatible power supply modules are installed. CPU and SB bus configurations also affect the number of available I/O positions. Therefore, the maximum I/O count should be checked against the complete controller configuration rather than treated as a fixed capacity for every arrangement.
Unused module positions require the appropriate dummy covers. Yokogawa identifies NFDCV01 for unused I/O module slots and NFDCV02 for unused power supply slots. These accessories should be considered when checking the completeness of a base module assembly.
Frequently Asked Questions
Q: How many I/O modules can the NFBU200 accommodate?
A: Up to 8 I/O modules can be installed in a standard control-unit configuration. CPU redundancy and SB bus repeater configurations occupy additional slots and reduce the available I/O capacity.
Q: Does the NFBU200 support redundant power supplies?
A: Yes. Its two power supply slots support a redundant arrangement with the specified compatible power supply module. The exact power supply model must be checked against the controller configuration.
Q: Are dummy covers required for unused slots?
A: Yes. Use NFDCV01 for unused I/O slots and NFDCV02 for unused power supply slots, as specified by Yokogawa.
Tags:
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.