Skip to product information
1 of 3

NFAI835-S50

Brand: Yokogawa
Order Number: NFAI835-S50
Type: Analog I/O Module
Country:
Low stock: 15 left

Description

Caret Down

The Yokogawa NFAI835-S50 is an isolated analog I/O module designed to handle 4-20 mA field signals. It provides four analog input channels and four analog output channels, with isolation between the field signals, system interface, and individual channels. The module supports bidirectional analog signal interfacing within the Yokogawa FCN I/O platform.

Functional Description

The NFAI835-S50 combines analog input and output functions in one module. Its four input channels receive 4-20 mA signals from field instruments, while its four output channels provide 4-20 mA signals to external control devices.

Channel isolation separates individual signal circuits and provides electrical isolation between the I/O signals and the system. This arrangement is relevant when connecting multiple field circuits with different electrical reference potentials.

I/O Performance and Signal Isolation

The input channels have an accuracy of +/-0.1% of full scale, while the output channels have an accuracy of +/-0.3% of full scale. Both input and output data have a 10 ms refresh cycle. The input and output step response times are 100 ms, providing the timing reference for signal acquisition and output updates.

The module provides 500 V AC withstand voltage for 1 minute between the I/O signals and the system, and between individual channels. This electrical separation helps limit the transfer of electrical disturbances between field circuits and the controller interface.

Output Control and Field Signal Requirements

Each output channel supports a load resistance of 0 to 750 ohms. Circuit-open detection operates at 0.65 mA or less. The output fallback function can be configured by channel, with two available responses:

  • HOLD: Retains the output when fallback is detected.
  • SETV: Outputs a specified value when fallback is detected.

Fallback detection takes 4 seconds. This setting determines how the output behaves when the module detects a fallback condition and should be considered when configuring connected control devices.

Model and Suffix Identification

The NFAI835-S50 ordering code identifies the standard, basic version without explosion protection.

  • NFAI835: Analog I/O Module with four isolated 4-20 mA input channels and four isolated 4-20 mA output channels.
  • -S: Standard type.
  • 5: Without explosion protection.
  • 0: Basic type.

The specified configuration should not be confused with the -H HART communication version or the -E explosion-protected version.

Technical Specifications

Parameter Specification
Model NFAI835-S50
Brand Yokogawa
Product Type Isolated Analog I/O Module
Input Channels 4
Output Channels 4
Input Signal 4-20 mA
Output Signal 4-20 mA
Channel Isolation Individual channel isolation
Allowable Input Current 25 mA
Input Resistance 250 ohms (power ON)
Output Load Resistance 0-750 ohms
Circuit-Open Detection 0.65 mA or less
Input Accuracy +/-0.1% of full scale
Output Accuracy +/-0.3% of full scale
Data Refresh Cycle 10 ms
Input Step Response Time 100 ms
Output Step Response Time 100 ms
Withstand Voltage 500 V AC for 1 minute
Transmitter Power Supply 20.2-29.3 V
Output Fallback HOLD / SETV, configurable by channel
Fallback Detection Time 4 seconds
Maximum Current Consumption 360 mA (5 V DC)
Maximum Current Consumption 450 mA (24 V DC)
External Connection Pressure clamp terminal or MIL connector cable
Dimensions (W x H x D) 107.5 x 130 x 32.8 mm
Weight 0.3 kg

Installation and Connection Considerations

The module requires a 24 V DC supply to the analog field power supply terminal of the power supply module. The actual transmitter supply voltage available at the field connection is specified as 20.2 to 29.3 V, depending on the applied analog field supply voltage.

External field wiring can use a pressure clamp terminal or MIL connector cable. When using a MIL connector cable, the applicable withstand voltage depends on the electrical specifications of the selected cable.

The module's power consumption must also be included in the FCN power supply capacity calculation. Check both the 5 V DC system supply and 24 V DC analog field supply requirements against the installed power supply module ratings.

Frequently Asked Questions

Q: How many analog signals can the NFAI835-S50 handle?

A: It handles four 4-20 mA input signals and four 4-20 mA output signals. Both signal groups have individual channel isolation.

Q: Can the output channels retain their values during a fallback condition?

A: Yes. The output fallback function supports HOLD to retain the output or SETV to apply a configured value. The response can be configured separately for each output channel.

Q: Does the NFAI835-S50 support HART communication or explosion protection?

A: The -S50 configuration is the standard type without explosion protection. Yokogawa identifies -H as the HART communication option and -E as the explosion-protected option; these should not be assumed to be included in the -S50 version.


Product Benefits

Caret Down

Reviews

Caret Down

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)
View full details

Recommended products

Recently viewed product