NFAI141-H00
Description
Description
The Yokogawa NFAI141-H00 is a 16-channel analog input module designed for the STARDOM FCN controller platform. It accepts 4-20 mA current signals from field transmitters and supports HART communication for compatible instrument data exchange. Its non-isolated channel configuration and individual 2-wire or 4-wire transmitter settings make it suitable for multi-channel process signal acquisition.
Signal Processing and HART Communication
Each channel receives a 4-20 mA DC signal and converts the measured current into a digital value for the controller. The module has a specified accuracy of +/-0.1% of full scale, with a 10 ms data refresh cycle and a 100 ms input step response time.
HART communication allows compatible field instruments to exchange digital device information over the analog current loop. This provides access to instrument-related communication in addition to the primary process measurement.
Transmitter Configuration and Power
The module supports channel-by-channel selection of 2-wire or 4-wire transmitter connections through setting pins. For 2-wire transmitter operation, the analog field power supply terminal of the power supply module must receive 24 V DC. The available transmitter supply is 22.8 to 26.4 V, with a 27 mA output current limit.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | NFAI141-H00 |
| Brand | Yokogawa |
| Product Type | HART Analog Input Module |
| Platform | STARDOM FCN |
| Number of Channels | 16 |
| Input Signal | 4-20 mA DC |
| Channel Isolation | Non-isolated |
| Allowable Input Current | 27 mA |
| Input Resistance (Power ON) | 250 ohm |
| Input Resistance (Power OFF) | 500 kohm or more |
| Accuracy | +/-0.1% of full scale |
| Data Refresh Cycle | 10 ms |
| Input Step Response Time | 100 ms |
| Transmitter Power Supply | 22.8 to 26.4 V DC |
| Transmitter Supply Current Limit | 27 mA |
| Transmitter Configuration | 2-wire / 4-wire, channel by channel |
| Temperature Drift | Max. +/-0.01%/deg C |
| Maximum Current Consumption | 310 mA at 5 V DC |
| Maximum Current Consumption | 450 mA at 24 V DC |
| External Connection | Pressure clamp terminal or MIL connector cable |
| HART Communication | Available |
| Weight | 0.2 kg |
Source: Yokogawa General Specifications, GS 34P02Q31-01E.
Installation and Signal Isolation
NFAI141-H00 uses a non-isolated input architecture. The 16 channels do not provide individual channel-to-channel galvanic isolation, so the grounding arrangement and electrical potential differences between field circuits should be considered during system design.
For intrinsically safe applications, Yokogawa specifies the use of an isolation barrier. A Zener barrier must not be connected to this module.
Frequently Asked Questions
Q: Does NFAI141-H00 support HART communication?
A: Yes. The NFAI141-H series supports HART communication alongside 4-20 mA analog signal acquisition. Refer to Yokogawa GS 34P02Q53-01E for detailed HART function specifications.
Q: Can the module connect to both 2-wire and 4-wire transmitters?
A: Yes. Each channel can be configured for either 2-wire or 4-wire transmitter operation using the module setting pins. The required field power supply arrangement must also be considered.
Q: Are the 16 input channels electrically isolated?
A: No. NFAI141-H00 is a non-isolated analog input module. For intrinsically safe applications, use an isolation barrier rather than a Zener barrier.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.