ATSA3S-0
Description
Description
The Yokogawa ATSA3S-0 is a single-arrangement pressure clamp terminal block designed for analog input signal connections in Yokogawa field control systems. It provides 8 connection points for field wiring and is specified for use with the ASI133 analog input module with built-in barrier. It provides the field wiring interface between the analog input circuits and the I/O module.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | ATSA3S-0 |
| Brand | Yokogawa |
| Product Type | Pressure Clamp Terminal Block for Analog Input |
| Terminal Type | Pressure Clamp |
| Channel Capacity | 8 points |
| Connection Arrangement | Single |
| Compatible I/O Module | ASI133 |
| Signal Type | Analog Input |
| Suffix Code | -0 |
Function and Module Connection
The ATSA3S-0 provides the terminal connection interface for field analog input signals. It is paired with the ASI133, an 8-channel isolated analog input module supporting 4-20 mA signals.
The terminal block and I/O module perform different functions: the ATSA3S-0 handles field-side wiring connections, while the ASI133 processes the incoming analog signals for the control system. The terminal block should not be identified as an independent analog input processing module.
Mechanical and Environmental Specifications
The terminal block has a compact mounting profile for installation alongside the associated I/O hardware. Its pressure clamp connection provides the field wiring termination points without performing analog signal conversion.
The manufacturer's specification identifies the ATSA3S arrangement as having no surge absorber. This should be considered when checking the field-side protection requirements of the installation.
| Parameter | Specification |
|---|---|
| Dimensions (W x H x D) | 32.6 x 60.5 x 114 mm |
| Weight | Approx. 0.20 kg |
| Operating Temperature | -20 to 70 deg C |
| Corrosive Gas Resistance | ISA S71.04 Class G3 |
Model Identification and Configuration
Yokogawa distinguishes between single and dual-redundant pressure clamp terminal blocks:
- ATSA3S-0: Single arrangement for the ASI133 analog input module.
- ATSA3D-0: Dual-redundant arrangement for the ASI133 analog input module.
The ATSA3S-0 suffix code -0 is specified as a fixed code. It should be retained when identifying or ordering the complete terminal block model.
Frequently Asked Questions
Q: Which I/O module is compatible with the ATSA3S-0?
A: The specified connecting module is the Yokogawa ASI133 analog input module with built-in barrier. The terminal block is designed for the 8-channel analog input configuration.
Q: What is the difference between ATSA3S-0 and ATSA3D-0?
A: ATSA3S-0 is the single terminal block arrangement, while ATSA3D-0 is designed for dual-redundant analog input configurations. They are different hardware arrangements and should not be treated as interchangeable.
Q: Does the ATSA3S-0 provide surge protection?
A: No. Yokogawa's hardware specification identifies the ATSA3S arrangement as being supplied without a surge absorber. Check the field circuit protection requirements separately.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.