ASR133-S00/SR3S0
Description
Description
The Yokogawa ASR133-S00/SR3S0 is an 8-channel RTD/POT input module with a built-in barrier and isolated input circuits. It acquires resistance signals from resistance temperature detectors (RTDs) and potentiometers for processing by a Yokogawa control system. The specified configuration includes an ATSR3S-0 pressure clamp terminal connection for field wiring.
RTD and Potentiometer Signal Acquisition
The ASR133 accepts resistance-based field signals for temperature measurement and potentiometer position or resistance measurement. Its eight isolated input channels support the following sensor types:
- Platinum RTDs: Pt50, Pt100, Pt200, Pt500 and Pt1000.
- Nickel RTDs: Ni100, Ni120 and Ni200.
- Potentiometers: 0 to 10 kOhm.
RTD measurements use the resistance-temperature characteristics of the selected sensor to obtain temperature values. Potentiometer inputs provide resistance information that can represent the position of a connected measuring device. The supported sensor type and input configuration must be selected according to the field instrument.
Built-In Barrier and Input Isolation
The built-in barrier separates the field-side measurement circuits from the system-side interface. This arrangement is intended for applications requiring isolated resistance-signal acquisition. The module's isolation and barrier characteristics should be considered when checking field wiring and hazardous-area installation requirements.
Terminal Connection
The /SR3S0 option identifies the pressure clamp terminal configuration associated with the ASR133 module. Yokogawa documentation identifies the corresponding terminal model as ATSR3S-0. The pressure clamp arrangement provides the field connection for the RTD and potentiometer input signals.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | ASR133-S00/SR3S0 |
| Brand | Yokogawa |
| Product Type | RTD/POT Input Module |
| Input Channels | 8 |
| Input Isolation | Isolated |
| Barrier | Built-in barrier |
| RTD Types | Pt50, Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200 |
| Potentiometer Input | 0 to 10 kOhm |
| Terminal Connection | Pressure clamp terminal |
| Terminal Model | ATSR3S-0 |
| Operating Temperature | -20 to 70 deg C |
Frequently Asked Questions
Q: Which RTD sensor types are supported by the ASR133-S00/SR3S0?
A: It supports five platinum RTD types (Pt50, Pt100, Pt200, Pt500 and Pt1000) and three nickel RTD types (Ni100, Ni120 and Ni200).
Q: What is the function of the SR3S0 configuration?
A: /SR3S0 specifies the pressure clamp terminal option for RTD/POT signal connections. The corresponding Yokogawa terminal model is ATSR3S-0.
Q: Can this module accept potentiometer signals?
A: Yes. The module supports potentiometer inputs over a resistance range of 0 to 10 kOhm, in addition to the specified RTD sensor types.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.