ASD143-P00/SB4S0
Description
Description
The Yokogawa ASD143-P00/SB4S0 is a 16-channel digital input module with a built-in isolation barrier, designed for NAMUR-compatible field signal acquisition. It supports pulse counting and isolated status inputs. The complete order code specifies the pulse-count configuration and a pressure-clamp terminal block (ATSB4S-0) for field wiring.
Functional Description
The ASD143 is designed to acquire discrete signals from NAMUR-compatible field devices in accordance with IEC 60947-5-6. Its 16 isolated input channels allow field status signals to be transferred to the control system while maintaining electrical isolation at the field interface.
The built-in barrier provides an isolated interface for field signal connections. This is relevant when interfacing with field devices in applications requiring intrinsic-safety protection; actual hazardous-area installation must follow the applicable certification and system control-drawing requirements.
Input Functions
The module supports status input and pushbutton input. For status acquisition, the specified response time is 15 ms. Pushbutton detection requires a minimum ON duration of 20 ms, while the maximum ON/OFF cycle is 25 Hz.
The -P suffix identifies the pulse-count configuration. This allows the module to be selected for applications requiring pulse signal acquisition, subject to the specified input timing limits.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | ASD143-P00/SB4S0 |
| Brand | Yokogawa |
| Product Type | Digital Input Module with Built-In Barrier |
| Number of Input Channels | 16 |
| Input Signal | NAMUR compatible, IEC 60947-5-6 |
| Input Isolation | Galvanic isolation between field interface and system; no channel-to-channel isolation |
| Withstanding Voltage | 1500 V AC |
| Status Input Response Time | 15 ms |
| Minimum Pushbutton ON Detection Time | 20 ms |
| Maximum ON/OFF Cycle | 25 Hz |
| Maximum Current Consumption | 150 mA at 5 V DC; 110 mA at 24 V DC |
| Barrier Type | Isolated interface |
| Terminal Block | ATSB4S-0 |
| Terminal Connection | Pressure clamp terminal |
| Operating Temperature | -20 to 70 deg C |
| Environmental Classification | ISA S71.04 Class G3 |
| Weight | 0.3 kg |
Terminal Block and Model Configuration
The /SB4S0 option specifies the single pressure-clamp terminal block configuration for digital input connections. Yokogawa identifies the associated terminal block as ATSB4S-0. The corresponding dual-redundant terminal block is ATSB4D-0, ordered under the /SB4D0 option.
The distinction is important when checking replacement parts and cabinet wiring. The terminal block configuration should match the installed hardware arrangement rather than being selected solely from the ASD143 base model.
Hazardous-Area Interface
The built-in barrier provides the electrical interface for connecting compatible field devices in intrinsically safe circuits. Yokogawa documentation identifies the module family for installation in Zone 2 or Division 2 locations, with connections to field devices in Zone 0, Zone 1 or Division 1 under the applicable certification conditions.
The module's isolation is between the field interface and the control system, not between individual input channels. Hazardous-area installation requires verification of the relevant ATEX or FM certification, entity parameters, associated equipment and special conditions of use.
Frequently Asked Questions
Q: Does the ASD143-P00/SB4S0 support pulse counting?
A: Yes. Yokogawa defines the -P suffix as the pulse-count configuration. The specified maximum ON/OFF cycle is 25 Hz.
Q: Which terminal block is specified for ASD143-P00/SB4S0?
A: The specified terminal block is ATSB4S-0, a pressure-clamp terminal block for the single configuration. The dual-redundant option uses ATSB4D-0 and a different order-code suffix.
Q: Are the 16 input channels individually isolated?
A: No. The module provides galvanic isolation between the field interface and the system, but Yokogawa explicitly states that there is no isolation between individual channels. This distinction should be considered when reviewing field wiring and intrinsic-safety arrangements.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.