ANR10D-420/NDEL

Brand: Yokogawa
Order Number: ANR10D-420/NDEL
Type: Dual-Redundant ER Bus Node Unit
Country:
Low stock: 15 left

Description

Caret Down

The Yokogawa ANR10D-420/NDEL is a rack-mountable Node Unit for the Field Network I/O (FIO) system. It provides a remote-node interface between field I/O modules and a Field Control Unit (FCU) through the dual-redundant ER Bus. The unit also distributes power to installed I/O modules and connected field transmitters. The /NDEL option provides the software license for node expansion.

Functional Description

The ANR10D is designed for remote I/O configurations in which the node communicates with a local node through the ER Bus. An ER Bus Interface Master Module (EB401) installed in the local node provides the connection to the remote node.

The node accommodates power supply modules, ER Bus interface modules (EB501), and I/O modules. In a dual-redundant configuration, two power supply modules and two ER Bus interface modules are installed to provide redundant hardware paths.

Power Supply and Redundancy

The -4 configuration identifies a dual-redundant power supply arrangement. The 2 power-supply code identifies a 220-240 V AC supply operating at 50/60 Hz. The manufacturer's general specifications list a power consumption of 230 VA and 120 W for this AC supply configuration.

The /NDEL option is a node-expansion software license. Yokogawa specifies this license as mandatory when connecting with AFF50 or AFV10 equipment. It should not be confused with an additional hardware interface or power-supply module.

Node Capacity and System Connection

The manufacturer's FIO specifications define the ANR10D as a remote node rather than a local ESB Bus node. Up to eight remote nodes can be connected per ER Bus, subject to the FCU configuration and the applicable system-level connection limits.

The ER Bus connection requires an EB401 master module in the local node. The node-unit architecture separates field I/O installation from the FCU, allowing remote I/O modules to communicate with the controller through the ER Bus.

Technical Specifications

Parameter Specification
Model ANR10D-420/NDEL
Brand Yokogawa
Product Type Dual-Redundant ER Bus Node Unit
System FIO (Field Network I/O)
Bus Interface Dual-Redundant ER Bus
Power Supply 220-240 V AC, 50/60 Hz
Power Supply Configuration Dual-redundant
Electric Power Consumption 230 VA, 120 W
Mounting 19-inch rack
Dimensions (W x H x D) 482.6 x 221.5 x 205 mm
Weight 10 kg
Expansion Option /NDEL - Node Expansion Software License

Frequently Asked Questions

Q: What is the difference between ANR10D and ANB10D?

A: Both are dual-redundant FIO node units, but they serve different bus architectures. ANR10D is a remote node connected through the ER Bus, whereas ANB10D is a local node connected directly to the FCU through the ESB Bus.

Q: Is the /NDEL option required for every ANR10D installation?

A: The /NDEL license is specifically required when connecting with AFF50 or AFV10 equipment, according to Yokogawa's ordering specifications. Its requirement should therefore be checked against the intended FCU configuration.

Q: Does the ANR10D support redundant communication interfaces?

A: Yes. The dual-redundant configuration uses two ER Bus Interface Slave Modules (EB501). This provides a redundant interface arrangement for communication between the remote node and the local node.