The manufacturer identifies the ANB11D as a node unit for the dual-redundant ESB bus with optical repeater, designed for the CENTUM VP N-IO/FIO architecture. The model code ANB11D-B25 identifies a specific power-supply and optical-repeater configuration.

Functional Description

The ANB11D-B25 collects and relays remote I/O signals to a Field Control Unit (FCU) through the optical ESB bus. It supports the transmission of field analog signals and contact I/O signals over optical communication links while supplying power to the installed I/O modules and field transmitters.

The dual-redundant architecture uses redundant power supply modules and optical repeater slave modules. This configuration supports remote I/O communication over a specified optical transmission distance of 5 km.

Model Configuration

The complete model number identifies the following configuration:

Code Specification
ANB11D Dual-redundant ESB bus node unit with optical repeater
-B Dual-redundant power supply, 5 km optical repeater configuration
2 220-240 V AC power supply
5 Basic type without explosion protection

The -B configuration is specified for use with ANT411-□E, ANT411-□F, or A2EN501-□□1 on the master side. The corresponding optical repeater slave modules are selected according to the specified 5 km configuration.

Technical Specifications

Parameter Specification
Model ANB11D-B25
Brand Yokogawa
Product Type Optical ESB Bus Node Unit
System CENTUM VP
Bus Configuration Dual-redundant ESB bus
Optical Repeater Distance 5 km
Power Supply 220-240 V AC
Frequency 50/60 Hz
Power Consumption 230 VA, 120 W
I/O Module Capacity Maximum 8 modules
Power Supply Configuration Dual-redundant
Optical Repeater Configuration Dual-redundant
Mounting 19-inch rack
Mounting Screws 4 x M5
Weight 10 kg

Module Configuration and Signal Transmission

The ANB11D node unit accommodates several functional module types:

  • Power Supply Modules: Two power supply modules are used in the dual-redundant configuration. They supply power to the installed I/O modules and field transmitters.
  • Optical ESB Bus Repeater Slave Modules: Two repeater modules support the redundant optical communication arrangement.
  • I/O Modules: Up to eight I/O modules can be installed, subject to the applicable module allocation and installation restrictions.

The optical repeater configuration allows remote I/O signals to be transmitted between the node unit and the FCU. The optical ESB bus provides the communication path for field signal data.

Installation Considerations

The ANB11D-B25 is designed for 19-inch rack mounting using four M5 screws. An insulating bush is included as a standard accessory.

For safety and EMC compliance, Yokogawa specifies installation in a keyed metallic cabinet. I/O module quantity and slot allocation must follow the applicable N-IO/FIO system installation restrictions.

Frequently Asked Questions

Q: What is the difference between ANB11D-B25 and ANB11D-D25?

A: Both configurations use dual-redundant power supplies and 220-240 V AC input. The -B configuration supports the 5 km optical repeater arrangement, whereas -D specifies the 50 km configuration.

Q: Which optical repeater master modules are compatible with ANB11D-B25?

A: The documented master-side configurations are ANT411-□E, ANT411-□F, and A2EN501-□□1. The corresponding optical repeater slave configuration must also be selected according to the 5 km arrangement.

Q: Does ANB11D-B25 include explosion protection?

A: No. The suffix code 5 identifies the basic type without explosion protection. Explosion-protected configurations use different suffix codes and must be selected according to the applicable hazardous-area requirements.


Product Benefits