ANB11D-225/BU2B

Brand: Yokogawa
Order Number: ANB11D-225/BU2B
Type: Node Unit for Dual-Redundant ESB Bus with Optical Repeater
Country:
Low stock: 15 left

Description

Caret Down

The Yokogawa ANB11D-225/BU2B is a node unit for Yokogawa's dual-redundant ESB Bus architecture, designed for N-IO/FIO system configurations with optical bus transmission. This configuration specifies dual-redundant power supply, a 220-240 V AC supply, a 5 km optical repeater arrangement, and a BU2B connector unit with an ESB Bus terminator. It is the basic version without explosion protection.

Functional Description

The ANB11D provides the node-level hardware platform for installing power supply modules, bus interface modules, and communication modules. It connects the node to the ESB Bus architecture, while its optical repeater arrangement supports communication over fiber-optic links.

The dual-redundant power supply configuration provides two power supply paths. This arrangement supports continued node power availability if one supply path becomes unavailable, subject to the installed power modules and system configuration.

Power Supply and Optical Bus Configuration

The -2 suffix identifies the dual-redundant power supply arrangement for a 5 km optical repeater configuration. The optical repeater slave modules are specified as two ANT502 modules for the dual-redundant arrangement. The power supply section also uses two power supply modules, selected from PW481, PW482, or PW484 according to the applicable configuration.

The 5 km optical arrangement requires a compatible master-side module. Yokogawa specifies ANT401-□0 or ANT401-□3 for the master side when using the ANB11D-2 configuration. The optical link configuration should therefore be checked at both ends rather than selected solely by the node unit model.

Connector and Termination

The /BU2B option identifies a connector unit with an ESB Bus terminator. The terminator is part of the specified bus connection configuration and distinguishes this ordering option from /BU2A, which specifies a connector unit without a terminator.

Technical Specifications

Parameter Specification
Model ANB11D-225/BU2B
Brand Yokogawa
Product Type Node Unit for Dual-Redundant ESB Bus with Optical Repeater
System Application N-IO/FIO
Power Supply 220-240 V AC
Power Supply Frequency 50/60 Hz
Power Supply Configuration Dual-redundant
Optical Repeater Distance 5 km
Optical Repeater Slave Modules 2 x ANT502
Power Supply Modules 2 x PW481, PW482, or PW484
Maximum I/O Module Capacity 8
Power Consumption 230 VA, 120 W
Connector Unit BU2B, with ESB Bus terminator
Explosion Protection Basic type, no explosion protection
Mounting 19-inch rack mount, 4 x M5 screws
Dimensions (W x H x D) 482.6 x 221.5 x 205 mm
Weight 10 kg

Specifications based on Yokogawa GS 33J60F30-01EN. The weight is for the stated populated configuration, not necessarily the bare node unit.

Installation and Configuration Notes

  • Install the node unit in a keyed metallic cabinet to meet the specified safety and EMC requirements.
  • Confirm that the optical repeater master and slave modules match the selected 5 km configuration.
  • Observe the permitted module quantity and slot allocation when installing I/O modules.
  • The node unit supports up to 8 I/O modules; actual module combinations remain subject to system configuration restrictions.

Frequently Asked Questions

Q: Does ANB11D-225/BU2B support a 50 km optical link?

A: No. The -2 configuration specifies the 5 km optical repeater arrangement. The ANB11D -4 configuration is specified for a 50 km optical repeater arrangement and requires the corresponding master-side equipment.

Q: Which optical repeater modules are specified for this model?

A: The dual-redundant 5 km configuration uses two ANT502 optical ESB Bus repeater slave modules. The master side is specified as ANT401-□0 or ANT401-□3.

Q: Does the BU2B option include an ESB Bus terminator?

A: Yes. /BU2B specifies a connector unit with an ESB Bus terminator. The /BU2A option specifies a connector unit without the terminator.