ANB10D-427/CU2N
Description
Description
The Yokogawa ANB10D-427/CU2N is an ESB Bus Node Unit designed for dual-redundant Extended Serial Backboard (ESB) bus communication in Yokogawa CENTUM VP control systems. It provides the interface between field I/O modules and the Field Control Unit (FCU), while distributing power to installed I/O modules. This configuration includes dual-redundant power supplies, a 220-240 V AC input, ISA Standard G3 coating, and two ESB bus connector units.
Functional Description
The ANB10D serves as a node-level interface between field I/O modules and the FCU. It transfers analog and contact I/O signals through the ESB bus, allowing the controller to exchange field data with the remote I/O node.
In addition to bus communication, the unit distributes power to the installed I/O modules and supports transmitter power supply through its power supply configuration. The dual-redundant architecture provides two power supply modules and two ESB bus interface slave modules.
Ordering Configuration
The complete model number identifies the main hardware configuration and included bus connection accessories.
| Parameter | Specification |
|---|---|
| Model | ANB10D-427/CU2N |
| Brand | Yokogawa |
| Product Type | ESB Bus Node Unit |
| System Family | CENTUM VP |
| Node Configuration | Dual-redundant ESB bus |
| Power Supply Configuration | Dual-redundant |
| Power Input | 220-240 V AC |
| Input Frequency | 50/60 Hz |
| Environmental Coating | ISA Standard G3 |
| Explosion Protection | No explosion protection |
| ESB Bus Connector | 2 x S9562FA |
| Maximum I/O Module Capacity | 8 modules |
| Power Consumption | 230 VA, 120 W |
| Mounting | 19-inch rack |
| Power Supply Module | PW482 configuration |
| ESB Bus Interface Module | SB401 |
Suffix and Option Code Identification
The ordering code ANB10D-427/CU2N identifies the following configuration:
| Code | Description |
|---|---|
| ANB10D | Node Unit for Dual-Redundant ESB Bus |
| -4 | Dual-redundant power supply |
| 2 | 220-240 V AC power supply |
| 7 | ISA Standard G3 option, without explosion protection |
| /CU2N | Two ESB bus connector units, part number S9562FA |
The /CU2N option specifies two connector units for ESB bus connections. It differs from /CU2T, which specifies two connector units with terminators (S9564FA). These options should not be treated as interchangeable when checking an existing system configuration.
Power Supply and Bus Configuration
The 220-240 V AC input operates at 50/60 Hz. The dual-redundant power configuration uses two power supply modules, while two SB401 ESB Bus Interface Slave Modules provide the corresponding redundant bus interface arrangement.
The specified electrical consumption is 230 VA and 120 W. These values describe the node unit's electrical consumption and should not be confused with the total power capacity available to connected field devices.
Installation and System Connection
The ANB10D is designed for 19-inch rack mounting using four M5 mounting screws. When connecting the node unit to an FCU, the ESB Bus Coupler Module EC401 or EC402 is required.
For a dual-redundant FCU configuration, EC401 or EC402 modules must be installed in both slots 7 and 8. For a single ESB bus configuration, the coupler module is installed in slot 7, with slot 8 left empty.
The node unit supports up to eight I/O modules. Actual module allocation and installation conditions must be checked against the applicable CENTUM VP FIO or N-IO system configuration requirements.
Frequently Asked Questions
Q: What is the difference between ANB10D and ANB11D?
A: ANB10D is a node unit for a dual-redundant ESB bus. ANB11D is designed for a dual-redundant ESB bus with an optical repeater. The two models have different node configurations and should be selected according to the required bus architecture.
Q: Does ANB10D-427/CU2N include ESB bus terminators?
A: No. The /CU2N option specifies two standard ESB bus connector units, part number S9562FA. The /CU2T option specifies two connector units with terminators, part number S9564FA.
Q: Which ESB Bus Coupler Module is required to connect ANB10D to an FCU?
A: Yokogawa specifies EC401 or EC402 for this connection. Both slots 7 and 8 require coupler modules in a dual-redundant configuration. The required arrangement depends on the FCU bus configuration.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.