Skip to product information
1 of 3

ANB10D-427/CU2N

Brand: Yokogawa
Order Number: ANB10D-427/CU2N
Type: ESB Bus Node Unit
Country:
Low stock: 15 left

Description

Caret Down

The Yokogawa ANB10D-427/CU2N is an ESB Bus Node Unit designed for dual-redundant Extended Serial Backboard (ESB) bus communication in Yokogawa CENTUM VP control systems. It provides the interface between field I/O modules and the Field Control Unit (FCU), while distributing power to installed I/O modules. This configuration includes dual-redundant power supplies, a 220-240 V AC input, ISA Standard G3 coating, and two ESB bus connector units.

Functional Description

The ANB10D serves as a node-level interface between field I/O modules and the FCU. It transfers analog and contact I/O signals through the ESB bus, allowing the controller to exchange field data with the remote I/O node.

In addition to bus communication, the unit distributes power to the installed I/O modules and supports transmitter power supply through its power supply configuration. The dual-redundant architecture provides two power supply modules and two ESB bus interface slave modules.

Ordering Configuration

The complete model number identifies the main hardware configuration and included bus connection accessories.

Parameter Specification
Model ANB10D-427/CU2N
Brand Yokogawa
Product Type ESB Bus Node Unit
System Family CENTUM VP
Node Configuration Dual-redundant ESB bus
Power Supply Configuration Dual-redundant
Power Input 220-240 V AC
Input Frequency 50/60 Hz
Environmental Coating ISA Standard G3
Explosion Protection No explosion protection
ESB Bus Connector 2 x S9562FA
Maximum I/O Module Capacity 8 modules
Power Consumption 230 VA, 120 W
Mounting 19-inch rack
Power Supply Module PW482 configuration
ESB Bus Interface Module SB401

Suffix and Option Code Identification

The ordering code ANB10D-427/CU2N identifies the following configuration:

Code Description
ANB10D Node Unit for Dual-Redundant ESB Bus
-4 Dual-redundant power supply
2 220-240 V AC power supply
7 ISA Standard G3 option, without explosion protection
/CU2N Two ESB bus connector units, part number S9562FA

The /CU2N option specifies two connector units for ESB bus connections. It differs from /CU2T, which specifies two connector units with terminators (S9564FA). These options should not be treated as interchangeable when checking an existing system configuration.

Power Supply and Bus Configuration

The 220-240 V AC input operates at 50/60 Hz. The dual-redundant power configuration uses two power supply modules, while two SB401 ESB Bus Interface Slave Modules provide the corresponding redundant bus interface arrangement.

The specified electrical consumption is 230 VA and 120 W. These values describe the node unit's electrical consumption and should not be confused with the total power capacity available to connected field devices.

Installation and System Connection

The ANB10D is designed for 19-inch rack mounting using four M5 mounting screws. When connecting the node unit to an FCU, the ESB Bus Coupler Module EC401 or EC402 is required.

For a dual-redundant FCU configuration, EC401 or EC402 modules must be installed in both slots 7 and 8. For a single ESB bus configuration, the coupler module is installed in slot 7, with slot 8 left empty.

The node unit supports up to eight I/O modules. Actual module allocation and installation conditions must be checked against the applicable CENTUM VP FIO or N-IO system configuration requirements.

Frequently Asked Questions

Q: What is the difference between ANB10D and ANB11D?

A: ANB10D is a node unit for a dual-redundant ESB bus. ANB11D is designed for a dual-redundant ESB bus with an optical repeater. The two models have different node configurations and should be selected according to the required bus architecture.

Q: Does ANB10D-427/CU2N include ESB bus terminators?

A: No. The /CU2N option specifies two standard ESB bus connector units, part number S9562FA. The /CU2T option specifies two connector units with terminators, part number S9564FA.

Q: Which ESB Bus Coupler Module is required to connect ANB10D to an FCU?

A: Yokogawa specifies EC401 or EC402 for this connection. Both slots 7 and 8 require coupler modules in a dual-redundant configuration. The required arrangement depends on the FCU bus configuration.