ANB10D-426/CU2N/NDEL
Description
Description
The Yokogawa ANB10D-426/CU2N/NDEL is a dual-redundant ESB Bus Node Unit designed to connect Field Network I/O (FIO) modules to the CENTUM VP control system. It features dual-redundant power supplies, a 220-240 V AC power configuration, ISA Standard G3 environmental protection, and an extended operating temperature option. The /CU2N and /NDEL options specify the ESB bus connector units and node expansion software license.
Functional Description
The ANB10D provides the node interface between FIO modules and the dual-redundant ESB bus. It forms part of the distributed I/O architecture, allowing field input and output signals to be exchanged with the Field Control Station (FCS) through the ESB communication network.
The dual-redundant configuration provides two power supply paths. This arrangement supports power continuity if one supply path becomes unavailable, subject to the installed power supply configuration and system conditions.
Power Supply and Environmental Configuration
The -426 suffix defines three configuration elements:
- -4: Dual-redundant power supply.
- 2: 220-240 V AC power supply, 50/60 Hz.
- 6: ISA Standard G3 option, -20 to 70 deg C temperature option, and no explosion protection.
The G3 option provides environmental protection against corrosive contaminants. The temperature option specifies an extended operating range. Yokogawa's ordering specifications state that this combined G3 and temperature configuration is selectable when the ANB10 unit is connected to an Optical ESB Bus Node Unit (ANB11). This installation condition should be checked during system configuration.
ESB Bus Interface and Connector Options
The /CU2N option supplies two S9562FA ESB Bus Connector Units for the dual-redundant bus configuration. This provides the physical connector hardware for the two ESB bus paths.
The /NDEL option is the Software License for Node Expansion. Yokogawa specifies this option for connecting the node unit to the AFV10, AFV30, AFV40 and AFF50 Field Control Unit families in the applicable FIO configuration. It is a system-level licensing option rather than an additional communication module.
Hardware Configuration
The ANB10D hardware configuration supports the following module arrangement:
- Two PW481, PW482 or PW484 power supply modules for dual-redundant operation.
- Two SB401 ESB Interface Slave Modules for dual-redundant communication.
- Up to eight I/O modules, subject to system configuration and installation restrictions.
The power supply modules provide power to the installed I/O modules and field transmitters. The SB401 modules handle the ESB interface function. The actual I/O module allocation depends on the connected Field Control Unit and the applicable system configuration.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | ANB10D-426/CU2N/NDEL |
| Brand | Yokogawa |
| Product Type | Node Unit for Dual-Redundant ESB Bus |
| Bus Interface | Dual-Redundant ESB Bus |
| Power Supply Configuration | Dual-redundant |
| Rated Supply Voltage | 220-240 V AC |
| Supply Frequency | 50/60 Hz |
| Power Consumption | 230 VA, 120 W |
| Environmental Protection | ISA Standard G3 |
| Operating Temperature Option | -20 to 70 deg C |
| Explosion Protection | No |
| ESB Connector Option | /CU2N, 2 x S9562FA |
| Software Option | /NDEL, Node Expansion License |
| Power Supply Modules | 2 x PW481, PW482 or PW484 |
| ESB Interface Modules | 2 x SB401 |
| Maximum I/O Modules | 8 |
| Mounting | 19-inch rack |
| Mounting Screws | 4 x M5 |
| Dimensions (W x H x D) | 482.6 x 221.5 x 205 mm |
| Weight | 10 kg |
Installation and System Configuration
The ANB10D is designed for 19-inch rack mounting and uses four M5 mounting screws. When connecting the node unit to an applicable Field Control Unit, the ESB Bus Coupler Module EC401 or EC402 is required. For a dual configuration, the coupler modules occupy slots 7 and 8; for a single configuration, the coupler occupies slot 7 and slot 8 remains empty.
When installing FIO modules with built-in barriers, an insulating partition (Part No. T9083NA) must be fitted in the eighth slot. I/O module allocation and cabinet temperature restrictions must also be checked against the applicable system installation documentation.
Frequently Asked Questions
Q: Does the ANB10D-426/CU2N/NDEL support dual-redundant ESB communication?
A: Yes. The ANB10D is designed for a dual-redundant ESB bus configuration and uses two SB401 ESB Interface Slave Modules.
Q: What is included with the /CU2N option?
A: The /CU2N option specifies two S9562FA ESB Bus Connector Units. It is the connector configuration for the dual-redundant ANB10D node unit.
Q: Is the -20 to 70 deg C temperature range applicable to every ANB10D configuration?
A: No. The -6 suffix combines the ISA Standard G3 option with the extended temperature option and no explosion protection. Yokogawa specifies this combination for use when the ANB10 unit is connected to an ANB11 Optical ESB Bus Node Unit. The actual system connection must be verified before selection.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.