AFV30S-S31262
Description
Description
The Yokogawa AFV30S-S31262 is a 19-inch rack-mountable Field Control Unit (FCU) for the CENTUM VP FIO control system. It provides field control processing and Vnet/IP communication between the control station and distributed I/O node units. Its ordering configuration identifies dual-redundant Vnet/IP communication, a single power supply, and a 220-240 V AC supply option.
Functional Description
The AFV30S serves as the control processing unit of a Field Control Station (FCS). It manages control functions and communicates with field I/O through the FIO architecture. Its Vnet/IP interface provides a dual-redundant communication path between the FCU and the CENTUM VP control network.
The model is the single-power-supply configuration. The suffix code 3 specifies dual-redundant Vnet/IP communication, but does not indicate redundant power or dual-redundant processor modules.
Configuration and Communication
The AFV30S supports connections to ESB Bus Node Units (ANB10) and Optical ESB Bus Node Units (ANB11), with a maximum of 13 node units per FCU. ESB Bus Coupler Modules EC401 or EC402 are required for these connections.
For dual-redundant ESB bus arrangements, the coupler modules must be installed in both slots 7 and 8. A single ESB bus configuration uses slot 7, leaving slot 8 empty. Remote optical ESB connections require the appropriate optical repeater arrangement.
Power and Installation
The specified power supply is 220-240 V AC at 50/60 Hz, with a rated power consumption of 230 VA. The unit uses M4 screw terminals for power, grounding and READY contact connections. Network connections use UTP cable rated CAT5e or better to a Layer 2 switch.
The READY output provides normally closed (NC) and common (C) contacts. These contacts open when the FCU fails, allowing external equipment to monitor the controller's fault status. The contact rating is 30 V DC maximum and 0.3 A maximum.
Parameter | Specification
| Parameter | Specification |
|---|---|
| Model | AFV30S-S31262 |
| Brand | Yokogawa |
| Product Type | Field Control Unit (FCU) |
| System | CENTUM VP |
| Control System | FIO |
| Mounting | 19-inch rack mountable |
| Processor Type | CP461 |
| Communication Interface | Dual-redundant Vnet/IP |
| Power Supply | 220-240 V AC |
| Frequency | 50/60 Hz |
| Power Consumption | 230 VA |
| Power Supply Configuration | Single |
| READY Contact Output | 2 terminals (NC, C) |
| READY Contact Rating | 30 V DC, max. 0.3 A |
| Maximum Connectable Node Units | 13 per FCU |
| ESB Bus Coupler | EC401 or EC402 |
| Network Cable | UTP, CAT5e or better |
| Power Connection | M4 screw terminals |
| Grounding Connection | M4 screw terminal |
| Weight | 7.0 kg |
| Dimensions (W x H x D) | 482.6 x 265.9 x 207 mm |
| Memory Backup | Battery backup, max. 72 hours |
| Battery Recharge Time | Min. 48 hours |
Ordering Code Identification
The complete ordering code identifies the following configuration:
| Code | Description |
|---|---|
| AFV30S | Field Control Unit for FIO, 19-inch rack mountable |
| -S | Standard type for CP461 |
| 3 | Dual-redundant Vnet/IP, single power supply |
| 1 | Fixed code |
| 2 | 220-240 V AC power supply |
| 6 | ISA Standard G3 option, without explosion protection |
| 2 | Fixed code for CENTUM VP R6.01 or later |
The -S configuration identifies the CP461 processor platform. Yokogawa discontinued new ordering of the AFV30S configuration with CP461 following the processor supply termination on October 19, 2019. Existing units remain identifiable by their original ordering codes.
Frequently Asked Questions
Q: Does AFV30S-S31262 have redundant power supplies?
A: No. The suffix code 3 specifies dual-redundant Vnet/IP communication with a single power supply. It should not be confused with a dual-power configuration.
Q: Which processor is specified for AFV30S-S31262?
A: This model specifies the CP461 processor type. CP461 replacement with CP471 must be performed by a Yokogawa-authorized service engineer, not by the user. The applicable CENTUM VP software version and ESB coupler style must also be checked.
Q: Can AFV30S-S31262 connect directly to FIO node units?
A: ESB Bus Node Units and Optical ESB Bus Node Units require an EC401 or EC402 bus coupler arrangement. The required slot allocation depends on whether the ESB connection is single or dual redundant.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.