Skip to product information
1 of 3

AFV30S-S31262

Brand: Yokogawa
Order Number: AFV30S-S31262
Type: Field Control Unit
Country:
Low stock: 15 left

Description

Caret Down

The Yokogawa AFV30S-S31262 is a 19-inch rack-mountable Field Control Unit (FCU) for the CENTUM VP FIO control system. It provides field control processing and Vnet/IP communication between the control station and distributed I/O node units. Its ordering configuration identifies dual-redundant Vnet/IP communication, a single power supply, and a 220-240 V AC supply option.

Functional Description

The AFV30S serves as the control processing unit of a Field Control Station (FCS). It manages control functions and communicates with field I/O through the FIO architecture. Its Vnet/IP interface provides a dual-redundant communication path between the FCU and the CENTUM VP control network.

The model is the single-power-supply configuration. The suffix code 3 specifies dual-redundant Vnet/IP communication, but does not indicate redundant power or dual-redundant processor modules.

Configuration and Communication

The AFV30S supports connections to ESB Bus Node Units (ANB10) and Optical ESB Bus Node Units (ANB11), with a maximum of 13 node units per FCU. ESB Bus Coupler Modules EC401 or EC402 are required for these connections.

For dual-redundant ESB bus arrangements, the coupler modules must be installed in both slots 7 and 8. A single ESB bus configuration uses slot 7, leaving slot 8 empty. Remote optical ESB connections require the appropriate optical repeater arrangement.

Power and Installation

The specified power supply is 220-240 V AC at 50/60 Hz, with a rated power consumption of 230 VA. The unit uses M4 screw terminals for power, grounding and READY contact connections. Network connections use UTP cable rated CAT5e or better to a Layer 2 switch.

The READY output provides normally closed (NC) and common (C) contacts. These contacts open when the FCU fails, allowing external equipment to monitor the controller's fault status. The contact rating is 30 V DC maximum and 0.3 A maximum.

Parameter | Specification

Parameter Specification
Model AFV30S-S31262
Brand Yokogawa
Product Type Field Control Unit (FCU)
System CENTUM VP
Control System FIO
Mounting 19-inch rack mountable
Processor Type CP461
Communication Interface Dual-redundant Vnet/IP
Power Supply 220-240 V AC
Frequency 50/60 Hz
Power Consumption 230 VA
Power Supply Configuration Single
READY Contact Output 2 terminals (NC, C)
READY Contact Rating 30 V DC, max. 0.3 A
Maximum Connectable Node Units 13 per FCU
ESB Bus Coupler EC401 or EC402
Network Cable UTP, CAT5e or better
Power Connection M4 screw terminals
Grounding Connection M4 screw terminal
Weight 7.0 kg
Dimensions (W x H x D) 482.6 x 265.9 x 207 mm
Memory Backup Battery backup, max. 72 hours
Battery Recharge Time Min. 48 hours

Ordering Code Identification

The complete ordering code identifies the following configuration:

Code Description
AFV30S Field Control Unit for FIO, 19-inch rack mountable
-S Standard type for CP461
3 Dual-redundant Vnet/IP, single power supply
1 Fixed code
2 220-240 V AC power supply
6 ISA Standard G3 option, without explosion protection
2 Fixed code for CENTUM VP R6.01 or later

The -S configuration identifies the CP461 processor platform. Yokogawa discontinued new ordering of the AFV30S configuration with CP461 following the processor supply termination on October 19, 2019. Existing units remain identifiable by their original ordering codes.

Frequently Asked Questions

Q: Does AFV30S-S31262 have redundant power supplies?

A: No. The suffix code 3 specifies dual-redundant Vnet/IP communication with a single power supply. It should not be confused with a dual-power configuration.

Q: Which processor is specified for AFV30S-S31262?

A: This model specifies the CP461 processor type. CP461 replacement with CP471 must be performed by a Yokogawa-authorized service engineer, not by the user. The applicable CENTUM VP software version and ESB coupler style must also be checked.

Q: Can AFV30S-S31262 connect directly to FIO node units?

A: ESB Bus Node Units and Optical ESB Bus Node Units require an EC401 or EC402 bus coupler arrangement. The required slot allocation depends on whether the ESB connection is single or dual redundant.