AFF50D-H41201
Description
Description
The Yokogawa AFF50D-H41201 is a duplexed Field Control Unit (FCU) for Yokogawa's Field Control Station (FCS). It executes process control functions and manages communication between the control station and field I/O. The unit features a VR5432 processor, 32 MB of main memory, dual-redundant V net communication, and a dual-redundant ESB bus interface.
Functional Description
The AFF50D-H41201 serves as the processing unit of an FCS. It executes configured control functions and coordinates data exchange with field I/O through the communication interfaces. Its duplexed architecture provides redundant control and communication paths for the field control station.
The V net interface is dual-redundant. The ESB bus interface is also always dual-redundant on this specific model, rather than being selectable as a single or dual interface.
Processor and Memory Protection
The controller uses a VR5432 processor operating at 133 MHz and provides 32 MB of main memory. Battery-backed memory protection preserves the main memory contents for up to 72 hours following a power failure. The specified minimum battery recharge time is 48 hours.
This backup function protects stored control information during a power interruption; it should not be confused with the duplexed processor architecture or the unit's redundant communication interfaces.
Communication and Status Monitoring
The FCU provides the following communication and diagnostic interfaces:
- V net: Dual-redundant communication interface using 10BASE-2.
- ESB bus: Dual-redundant interface on the AFF50D-H41201.
- FCU status output: Two terminals, NC and C, for external status monitoring.
The FCU status contacts open during an FCU failure. Their contact rating is 30 V DC maximum at 0.3 A, allowing the status circuit to be incorporated into an appropriately rated external monitoring or alarm circuit.
Power Supply Configuration
The product specification identifies three supply voltage configurations across the AFF50D family: 100-120 V AC, 220-240 V AC, and 24 V DC. The corresponding power consumption figures are 200 VA, 230 VA, and 5.5 A, respectively.
The complete ordering code must be checked when identifying the installed power supply. The 220-240 V AC configuration is the relevant selection for the H41201 ordering variant.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | AFF50D-H41201 |
| Brand | Yokogawa |
| Product Type | Duplexed Field Control Unit |
| Product Family | AFF50 |
| Processor | VR5432, 133 MHz |
| Main Memory | 32 MB |
| Memory Protection | Battery-backed memory, maximum 72 hours |
| Battery Recharge Time | Minimum 48 hours |
| V net Interface | Dual-redundant, 10BASE-2 |
| ESB Bus Interface | Dual-redundant |
| FCU Status Output | 2 terminals (NC, C) |
| Status Contact Rating | 30 V DC, maximum 0.3 A |
| Status Contact Behavior | Contacts open during FCU failure |
| Power Supply | 220-240 V AC, 50/60 Hz |
| Power Consumption | 230 VA |
| Mounting | 19-inch rack-mountable |
| Weight | 8 kg |
The hardware specifications are based on the AFF50D product specification and the CENTUM system documentation.
Model Configuration
The ordering code identifies the compact duplexed FCU configuration. The documented suffix structure includes the following selections:
| Code | Description |
|---|---|
| AFF50D | Duplexed Field Control Unit for V net and FIO |
| -H | Compact type |
| 4 | Dual-redundant V net (10BASE-2) and dual-redundant power supply |
| 1 | Fixed code |
| 2 | 220-240 V AC power supply |
| 0 | Basic type |
| 1 | ISA Standard G3 option |
The H41201 configuration therefore identifies the 220-240 V AC version. The complete model number should be retained when ordering or checking an existing installation.
Frequently Asked Questions
Q: What is the difference between AFF50S and AFF50D?
A: AFF50S is the single FCU version, while AFF50D is the duplexed version. The AFF50D-H41201 provides a redundant control configuration with dual-redundant V net and ESB bus interfaces.
Q: What happens to the FCU status contacts when the controller fails?
A: The NC and C status contacts open during an FCU failure. The external monitoring circuit must be designed within the specified maximum contact rating of 30 V DC and 0.3 A.
Q: How long can the main memory be protected during a power failure?
A: Battery backup provides main memory protection for up to 72 hours. The specified minimum battery recharge time is 48 hours.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.