Skip to product information
1 of 3

AFF50D-H41201

Brand: Yokogawa
Order Number: AFF50D-H41201
Country:
Low stock: 15 left

Description

Caret Down

The Yokogawa AFF50D-H41201 is a duplexed Field Control Unit (FCU) for Yokogawa's Field Control Station (FCS). It executes process control functions and manages communication between the control station and field I/O. The unit features a VR5432 processor, 32 MB of main memory, dual-redundant V net communication, and a dual-redundant ESB bus interface.

Functional Description

The AFF50D-H41201 serves as the processing unit of an FCS. It executes configured control functions and coordinates data exchange with field I/O through the communication interfaces. Its duplexed architecture provides redundant control and communication paths for the field control station.

The V net interface is dual-redundant. The ESB bus interface is also always dual-redundant on this specific model, rather than being selectable as a single or dual interface.

Processor and Memory Protection

The controller uses a VR5432 processor operating at 133 MHz and provides 32 MB of main memory. Battery-backed memory protection preserves the main memory contents for up to 72 hours following a power failure. The specified minimum battery recharge time is 48 hours.

This backup function protects stored control information during a power interruption; it should not be confused with the duplexed processor architecture or the unit's redundant communication interfaces.

Communication and Status Monitoring

The FCU provides the following communication and diagnostic interfaces:

  • V net: Dual-redundant communication interface using 10BASE-2.
  • ESB bus: Dual-redundant interface on the AFF50D-H41201.
  • FCU status output: Two terminals, NC and C, for external status monitoring.

The FCU status contacts open during an FCU failure. Their contact rating is 30 V DC maximum at 0.3 A, allowing the status circuit to be incorporated into an appropriately rated external monitoring or alarm circuit.

Power Supply Configuration

The product specification identifies three supply voltage configurations across the AFF50D family: 100-120 V AC, 220-240 V AC, and 24 V DC. The corresponding power consumption figures are 200 VA, 230 VA, and 5.5 A, respectively.

The complete ordering code must be checked when identifying the installed power supply. The 220-240 V AC configuration is the relevant selection for the H41201 ordering variant.

Technical Specifications

Parameter Specification
Model AFF50D-H41201
Brand Yokogawa
Product Type Duplexed Field Control Unit
Product Family AFF50
Processor VR5432, 133 MHz
Main Memory 32 MB
Memory Protection Battery-backed memory, maximum 72 hours
Battery Recharge Time Minimum 48 hours
V net Interface Dual-redundant, 10BASE-2
ESB Bus Interface Dual-redundant
FCU Status Output 2 terminals (NC, C)
Status Contact Rating 30 V DC, maximum 0.3 A
Status Contact Behavior Contacts open during FCU failure
Power Supply 220-240 V AC, 50/60 Hz
Power Consumption 230 VA
Mounting 19-inch rack-mountable
Weight 8 kg

The hardware specifications are based on the AFF50D product specification and the CENTUM system documentation.

Model Configuration

The ordering code identifies the compact duplexed FCU configuration. The documented suffix structure includes the following selections:

Code Description
AFF50D Duplexed Field Control Unit for V net and FIO
-H Compact type
4 Dual-redundant V net (10BASE-2) and dual-redundant power supply
1 Fixed code
2 220-240 V AC power supply
0 Basic type
1 ISA Standard G3 option

The H41201 configuration therefore identifies the 220-240 V AC version. The complete model number should be retained when ordering or checking an existing installation.

Frequently Asked Questions

Q: What is the difference between AFF50S and AFF50D?

A: AFF50S is the single FCU version, while AFF50D is the duplexed version. The AFF50D-H41201 provides a redundant control configuration with dual-redundant V net and ESB bus interfaces.

Q: What happens to the FCU status contacts when the controller fails?

A: The NC and C status contacts open during an FCU failure. The external monitoring circuit must be designed within the specified maximum contact rating of 30 V DC and 0.3 A.

Q: How long can the main memory be protected during a power failure?

A: Battery backup provides main memory protection for up to 72 hours. The specified minimum battery recharge time is 48 hours.


Product Benefits

Caret Down

Reviews

Caret Down

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)
View full details

Recommended products