ADV551-P60/D5S00
Description
Description
The Yokogawa ADV551-P60/D5S00 is a 32-channel, 24 V DC isolated digital output module designed to generate transistor-based switching signals for field devices. It supports current-sink outputs, pulse-width output and time-proportional output functions. This configuration includes a front-panel status display and an ATD5S-00 pressure clamp terminal block for field wiring.
Functional Description
The ADV551 provides 32 discrete output channels for transmitting controller commands to field-side loads. Its current-sink output architecture switches the external 24 V DC field circuit, allowing the control system to operate compatible loads through individual transistor output stages.
The module supports both conventional status outputs and pulse-based control. Its pulse-width and time-proportional output functions allow the controller to represent a variable control demand through the duration or proportion of an output pulse.
Model Configuration
The complete ordering code identifies the module hardware and its terminal connection arrangement:
| Code | Specification |
|---|---|
| ADV551 | 32-channel, 24 V DC isolated Digital Output Module |
| -P | With pulse-width output and time-proportional output functions |
| 6 | With status display; without explosion protection |
| 0 | Basic type |
| /D5S00 | With ATD5S-00 pressure clamp terminal block for digital output |
The /D5S00 option specifies the field wiring interface. It should not be confused with /D5A00, which specifies a different KS cable interface adapter.
Output Characteristics and Electrical Limits
The output channels use a 24 V DC current-sink configuration. The external field supply must remain within 20.4 to 26.4 V DC. Each channel supports a maximum load current of 100 mA at 26.4 V DC, while the specified load reference is 24 V DC at 50 mA.
The output ON voltage is limited to 2 V DC, and the maximum leakage current in the OFF state is 0.1 mA. These values are relevant when checking the switching thresholds and OFF-state behavior of connected field devices. When driving a DC relay, Yokogawa specifies the use of a diode.
Pulse Output and Channel Assignment
The ADV551 supports three output modes:
- Status Output (SO): Conventional ON/OFF switching controlled by the system.
- Pulse Width Output (PW): Generates a one-shot pulse with a configurable width.
- Time-Proportioning Output (TP): Controls the ON/OFF proportion over a defined time interval.
The pulse-width range is 8 ms to 7,200 s, with an 8 ms resolution. The specified response time is 3 ms or less for status outputs and 10 ms or less for mixed status and pulse outputs.
Pulse-width output requires two consecutive terminal numbers, with the first terminal being odd-numbered. The allocation of PW and TP functions must follow Yokogawa's channel assignment rules. In particular, the next terminal cannot be assigned a different function when an odd-numbered terminal is configured for PW.
Electrical Isolation and Field Wiring
The output signal circuits are isolated from the system side, with a specified withstand voltage of 2 kV AC for one minute. The output commons are arranged in common-minus groups of 16 channels, with a specified withstand voltage of 500 V AC between commons.
The /D5S00 configuration uses the ATD5S-00 pressure clamp terminal block. This provides the field wiring connection for the 32-channel output module. The terminal arrangement and common grouping should be considered when connecting loads that use different field power circuits.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | ADV551-P60/D5S00 |
| Brand | Yokogawa |
| Product Type | Digital Output Module |
| Number of Output Channels | 32 |
| Rated Applied Voltage | 24 V DC |
| External Power Supply Voltage Range | 20.4 to 26.4 V DC |
| External Power Supply Rating | 24 V DC, 50 mA |
| Output Format | Current sink |
| Maximum Load Current | 100 mA/channel at 26.4 V DC |
| Output ON Voltage | 2 V DC maximum |
| OFF-State Leakage Current | 0.1 mA maximum |
| Output Response Time | 3 ms or less (status output); 10 ms or less (mixed status and pulse outputs) |
| Pulse Width Range | 8 ms to 7,200 s |
| Pulse Width Resolution | 8 ms, with an additional ON/OFF delay of up to 1 ms |
| Signal-to-System Withstand Voltage | 2 kV AC for 1 minute |
| Withstand Voltage Between Commons | 500 V AC for 1 minute |
| Common Configuration | Common-minus side every 16 channels |
| Maximum Current Consumption | 700 mA at 5 V DC; 60 mA from external power supply |
| External Connection | ATD5S-00 pressure clamp terminal block |
| Module Weight | 0.20 kg |
| Dimensions | 107.5 x 32.8 x 130 mm |
Frequently Asked Questions
Q: Does the ADV551-P60/D5S00 support pulse-width and time-proportioning outputs?
A: Yes. The -P suffix identifies the pulse-width and time-proportioning output functions. These modes can be assigned according to the module's channel configuration rules.
Q: What is the difference between the D5S00 and D5A00 options?
A: /D5S00 specifies the ATD5S-00 pressure clamp terminal block, whereas /D5A00 specifies the ATD5A-00 KS cable interface adapter. They represent different field connection arrangements.
Q: Can the module directly drive a DC relay?
A: The output can drive compatible DC relay loads within its specified voltage and current limits. Yokogawa specifies that a diode must be connected when driving a DC relay. Check the relay coil current against the 100 mA per-channel maximum.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.