AAP149-S00
Description
Description
The Yokogawa AAP149-S00 is a 16-channel pulse input module compatible with PM1. It receives pulse train signals from pulse input signal conditioner cards and counts incoming pulses for use by the control system. The module supports non-isolated transistor contact inputs, with an input frequency range of 0 to 6 kHz and a data update period of 2 ms.
Pulse Input Function
The AAP149-S00 processes pulse signals from field signal conditioning equipment. Each channel accepts a transistor contact (open collector) signal and detects pulses on the trailing edge. The module counts the incoming pulses and makes the resulting data available to the control system.
Its 16 input channels share a non-isolated configuration. Unlike isolated pulse input modules, the AAP149 does not provide channel-to-channel or field-to-system electrical isolation as part of its specified input design.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | AAP149-S00 |
| Brand | Yokogawa |
| Product Type | Pulse Input Module |
| System Compatibility | PM1 compatible |
| Number of Input Channels | 16 |
| Channel Isolation | Non-isolated |
| Input Signal | Transistor contact (open collector) |
| Input Frequency | 0 to 6 kHz |
| Pulse Detection Edge | Trailing edge |
| Data Update Period | 2 ms |
| Maximum Current Consumption | 400 mA (5 V DC) |
| External Connection | Dedicated cable (KS2) |
| Weight | 0.30 kg |
Electrical Signal and Data Processing
The 0 to 6 kHz input frequency range defines the supported pulse repetition rate. The trailing-edge detection method determines which signal transition is counted as a pulse event. This distinction matters when checking the output of the upstream pulse signal conditioner.
The 2 ms data update period specifies how frequently updated input data is made available to the system. It should not be interpreted as the minimum pulse width or as a guaranteed end-to-end control response time.
Ordering Configuration
The AAP149 model uses the following suffix structure:
| Code | Description |
|---|---|
| -S | Standard type |
| 0 | Always 0 |
| 0 | Basic type |
| 1 | ISA Standard G3 option |
The AAP149-S00 ordering code identifies the standard, basic configuration. The final digit is not the ISA Standard G3 option; that configuration is identified by AAP149-S01.
Frequently Asked Questions
Q: How many pulse input channels does the AAP149-S00 provide?
A: It provides 16 non-isolated pulse input channels. Each channel accepts a transistor contact (open collector) signal.
Q: What is the maximum supported input frequency?
A: The specified input frequency range is 0 to 6 kHz. Pulse detection is performed on the trailing edge.
Q: What connection cable is required for the AAP149-S00?
A: The specified external connection is a dedicated KS2 cable. The cable and associated interface arrangement should be checked against the installed PM1 configuration before replacement or installation.
Tags:
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews