AAP135-S53/K4A00
Description
Description
The Yokogawa AAP135-S53/K4A00 is an 8-channel isolated pulse input module designed to receive and count contact ON/OFF signals, voltage pulses, and current pulses in a control system. It supports input frequencies up to 10 kHz and provides electrical isolation between the field inputs, individual channels, and the system. The /K4A00 ordering option specifies a KS Cable Interface Adapter.
Functional Description
The AAP135 receives pulse signals from field devices and converts them into count data for processing by the control system. It supports both two-wire and three-wire input arrangements, including contact signals and externally powered pulse signals.
Its eight input channels are electrically isolated from one another and from the system side. This separation helps limit the propagation of electrical disturbances between field signal circuits.
Input Signal and Counting Characteristics
The module accepts three principal signal types:
- Contact ON/OFF: Signals from relay contacts or transistor contacts.
- Voltage pulse: Voltage-level pulse signals from field instruments.
- Current pulse: Current-based pulse signals, internally converted to voltage for input processing.
The input frequency range of 0 to 10 kHz supports pulse-counting applications where signal frequency represents the operating rate or accumulated quantity of a field process. The minimum input pulse width is 40 us.
Electrical Isolation and Signal Conditioning
The module provides withstand voltage of 500 V AC for 1 minute between the input and system sides, and between individual input channels. This isolation arrangement allows separate field signal circuits to be connected without directly sharing their signal reference.
Additional signal-conditioning functions include:
- Selectable shunt resistance: None, 200 ohm, 500 ohm, or 1000 ohm.
- Pull-up resistance: 68 kohm, selectable for 12 V DC or 24 V DC.
- Configurable filtering for eliminating contact chattering.
- Selectable transmitter power supply: 12 V DC or 24 V DC.
For dry-contact inputs, the chatter-elimination filter is specified for signals up to 10 Hz.
Ordering Configuration
The complete ordering code identifies the module type, environmental configuration, and cable interface option.
| Code | Specification |
|---|---|
| AAP135 | 8-channel isolated Pulse Input Module |
| -S | Standard type |
| 5 | Without explosion protection |
| 3 | ISA Standard G3 option and temperature option (-20 to 70 deg C) |
| /K4A00 | KS Cable Interface Adapter, model ATK4A-00 |
The AAP135-S53/K4A00 therefore combines the standard, non-explosion-protected module configuration with the ISA G3 and extended-temperature options, together with the specified KS cable interface adapter.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | AAP135-S53/K4A00 |
| Brand | Yokogawa |
| Product Type | Pulse Input Module |
| Number of Input Channels | 8, isolated |
| Input Signal | Contact ON/OFF, voltage pulse, current pulse |
| Input Configuration | 2-wire and 3-wire |
| Input Frequency | 0 to 10 kHz |
| Minimum Input Pulse Width | 40 us |
| Data Update Period | 2 ms |
| Input-to-System Isolation | 500 V AC, 1 minute |
| Channel-to-Channel Isolation | 500 V AC, 1 minute |
| Contact Input Open Level | 100 kohm or higher |
| Contact Input Close Level | 200 ohm or lower |
| Voltage Pulse High Level | 3 to 24 V DC |
| Voltage Pulse Low Level | -1 to 8 V DC |
| Voltage Pulse Swing | 3 V or higher |
| Signal Source Resistance | 1 kohm or lower |
| Shunt Resistance | None / 200 / 500 / 1000 ohm |
| Pull-up Resistance | 68 kohm |
| Transmitter Power Supply | Selectable 12 V DC / 24 V DC |
| Power Supply Current Limit | 40 mA at 12 V DC; 30 mA at 24 V DC |
| Maximum Current Consumption | 300 mA (5 V DC), 400 mA (24 V DC) |
| Operating Temperature Option | -20 to 70 deg C |
| Explosion Protection | Without explosion protection |
| Environmental Option | ISA Standard G3 |
| Cable Interface Adapter | ATK4A-00 |
| Weight | 0.3 kg |
| External Connection | Pressure clamp terminal, KS cable, MIL connector cable |
Frequently Asked Questions
Q: Can the AAP135-S53/K4A00 receive both contact and voltage pulse signals?
A: Yes. It accepts contact ON/OFF, voltage pulse, and current pulse signals. The appropriate field wiring and input configuration depend on the signal source and connection method.
Q: Does the 10 kHz input frequency apply to all contact input configurations?
A: No. The general input frequency specification is 0 to 10 kHz, but the frequency is limited to 0 to 800 Hz between terminals B and C when receiving non-voltage contact signals. This distinction should be considered when selecting the input wiring.
Q: Is the AAP135-S53/K4A00 suitable for dual-redundant configurations?
A: The AAP135 module supports dual-redundant configuration. The shunt resistance is open on the standby side in a dual-redundant arrangement. The complete system configuration must follow the applicable Yokogawa installation requirements.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.