AAP135-S00/13S00
Description
Description
The Yokogawa AAP135-S00/13S00 is an 8-channel isolated pulse input module designed to receive contact ON/OFF, voltage pulse, and current pulse signals. It supports input frequencies up to 10 kHz and accepts both 2-wire and 3-wire field signal configurations. The /13S00 ordering option specifies a pressure clamp terminal block for pulse signal connections.
Functional Description
The AAP135 receives pulse signals from field devices and transfers the input information to the control system. Its eight channels are electrically isolated from one another and from the system side, allowing signals from separate field circuits to be handled independently.
Supported input signal configurations include:
- 2-wire signals: Contact ON/OFF, voltage pulse, and current pulse.
- 3-wire signals: Power-supply-type voltage pulse.
- Current pulse processing: Current input is converted to a voltage signal internally.
- Dual-redundant configuration: Supported by the module design.
Input Signal Characteristics
The module accepts pulse signals with frequencies from 0 to 10 kHz and a minimum pulse width of 40 us. For voltage and current pulse inputs, the specified high-level and low-level ranges determine the acceptable signal thresholds. The input source resistance must also be considered when selecting field transmitters.
For contact inputs, the module recognizes relay and transistor contact states using specified open- and closed-circuit resistance levels. A configurable filter is available to eliminate contact chattering.
Electrical Input Specifications
The input thresholds distinguish valid pulse states from noise or inactive signal levels. For voltage and current pulse inputs, the current signal is internally converted to voltage before processing.
- High-level voltage (VH): 3 to 24 V DC.
- Low-level voltage (VL): -1 to 8 V DC.
- Minimum voltage swing (VH - VL): 3 V.
- Maximum signal source resistance: 1 kOhm.
- Contact open resistance: 100 kOhm or more.
- Contact closed resistance: 200 Ohm or less.
The module also provides selectable shunt resistance values of none, 200 Ohm, 500 Ohm, or 1000 Ohm. Its 68 kOhm pull-up resistance supports 12 V DC or 24 V DC signal configurations.
Transmitter Power and Signal Conditioning
The transmitter power supply can be selected between 12 V DC and 24 V DC. The corresponding current limiter values are 40 mA at 12 V DC +/-10% and 30 mA at 24 V DC +/-10%.
A configurable filter handles contact chattering. For dry-contact pulse signals between terminals B and C, the specified input frequency range is limited to 0 to 800 Hz rather than the general 0 to 10 kHz rating.
Terminal Connection and Ordering Configuration
The /13S00 option identifies the ATI3S-00 pressure clamp terminal block for pulse signals. This provides a pressure-clamp field wiring interface for connecting the pulse input circuits.
The manufacturer's ordering information identifies the following configuration codes:
| Code | Description |
|---|---|
| -S | Standard type |
| 5 | Without explosion protection |
| E | With explosion protection |
| 0 | Basic type |
| 3 | ISA Standard G3 and temperature (-20 to 70 deg C) option |
| /13S00 | Pressure Clamp Terminal Block for Pulse, ATI3S-00 |
| /13S10 | Pressure Clamp Terminal Block for Pulse with surge absorber, ATI3S-10 |
| /13D00 | Dual Pressure Clamp Terminal Block for Pulse, ATI3D-00 |
| /13D10 | Dual Pressure Clamp Terminal Block for Pulse with surge absorber, ATI3D-10 |
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | AAP135-S00/13S00 |
| Brand | Yokogawa |
| Product Type | Pulse Input Module |
| Number of Input Channels | 8, isolated channels |
| Input Signal | Contact ON/OFF, voltage pulse, current pulse |
| Wiring Configuration | 2-wire and 3-wire |
| Input Frequency | 0 to 10 kHz |
| Dry Contact Input Frequency | 0 to 800 Hz between terminals B and C |
| Minimum Input Pulse Width | 40 us |
| High-Level Input Voltage | 3 to 24 V DC |
| Low-Level Input Voltage | -1 to 8 V DC |
| Minimum Voltage Swing | 3 V |
| Maximum Signal Source Resistance | 1 kOhm |
| Contact Open Resistance | 100 kOhm or more |
| Contact Closed Resistance | 200 Ohm or less |
| Shunt Resistance | None / 200 / 500 / 1000 Ohm |
| Pull-up Resistance | 68 kOhm |
| Filter | Configurable chattering elimination |
| Data Update Period | 2 ms |
| Transmitter Power Supply | Selectable 12 V DC / 24 V DC |
| Maximum Current Consumption | 300 mA (5 V DC), 400 mA (24 V DC) |
| Withstanding Voltage | 500 V AC for 1 minute, input-to-system and channel-to-channel |
| Redundant Configuration | Dual-redundant configuration supported |
| External Connection | Pressure clamp terminal block, KS cable, MIL connector cable |
| Terminal Block Option | ATI3S-00 |
| Weight | 0.3 kg |
Frequently Asked Questions
Q: How many pulse input channels does the AAP135-S00/13S00 provide?
A: It provides eight electrically isolated pulse input channels. Each channel supports the specified contact, voltage pulse, or current pulse input configurations.
Q: What is the function of the /13S00 suffix?
A: The /13S00 option specifies the ATI3S-00 pressure clamp terminal block for pulse signal connections. It identifies the terminal connection configuration rather than an additional input channel.
Q: Can the AAP135-S00/13S00 be used in a redundant configuration?
A: Yes. The AAP135 supports dual-redundant configuration. The module's isolation and shunt behavior are designed to support this arrangement, with the shunt circuit open on the standby side.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.