AAI543-H50/ATA4S-00
Description
Description
The Yokogawa AAI543-H50/ATA4S-00 is a 16-channel isolated analog output module that provides 4 to 20 mA current signals for field control devices. It supports HART digital communication and uses the ATA4S-00 pressure clamp terminal block for field wiring. Its specifications include a 10 ms data update period, circuit-open detection, and defined output isolation and load resistance limits.
Output Configuration and Signal Characteristics
The AAI543-H50 provides 16 isolated current output channels. Each channel delivers a 4 to 20 mA signal for analog control, allowing the system to transmit output commands to connected field devices.
- Output signal: 4 to 20 mA
- Number of channels: 16, isolated
- Allowable load resistance: 0 to 750 ohm
- Circuit-open detection: Less than 0.65 mA
- Accuracy: +/-48 uA
- Data update period: 10 ms
The 10 ms data update period specifies the interval at which output data is updated. Circuit-open detection provides an indication of an open output loop when the current falls below the specified threshold.
HART Communication and Terminal Connection
The HART-capable configuration supports digital communication over the analog current loop. This allows compatible field instruments to exchange digital information while using the 4 to 20 mA signal for the primary analog output.
The specified ATA4S-00 pressure clamp terminal block provides the field wiring interface. The listed external connection options also include a MIL connector cable and dedicated KS1 cable. The appropriate connection arrangement depends on the installed terminal and cable configuration.
Redundant Configuration and Switch-over Response
The H50 configuration identifies the standard switch-over response type for redundant operation without explosion protection. In a dual-redundant arrangement, two identical AAI543 modules with the same switch-over response type are used as control and standby modules.
During a control-to-standby switchover, the output may fall below 4 mA for a maximum of 100 ms. This timing is relevant when selecting the module for field devices that require continuous current output. The fast-response version has a different ordering code and should not be treated as equivalent to this standard-response configuration.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | AAI543-H50/ATA4S-00 |
| Brand | Yokogawa |
| Product Type | Analog Output Module |
| Number of Output Channels | 16, isolated |
| Output Signal | 4 to 20 mA |
| HART Communication | Available |
| Withstanding Voltage | 1500 V AC, 1 minute (output to system) |
| Allowable Load Resistance | 0 to 750 ohm |
| Circuit-Open Detection | Less than 0.65 mA |
| Output Accuracy | +/-48 uA |
| Data Update Period | 10 ms |
| Ambient Temperature Drift | +/-16 uA/10 deg C |
| Maximum Current Consumption | 230 mA (5 V DC), 540 mA (24 V DC) |
| External Connection | Pressure clamp terminal, MIL connector cable, dedicated KS1 cable |
| Terminal Block | ATA4S-00 |
| Weight | 0.4 kg |
Electrical Isolation and Load Requirements
The module provides 1500 V AC withstand voltage between the output circuit and the system for one minute. This specification defines the isolation withstand capability between these two sides; it should not be interpreted as a channel-to-channel isolation rating.
The allowable load resistance is 0 to 750 ohm. When connecting a field device, the total loop resistance, including wiring and connected equipment, must remain within the specified output load range.
Frequently Asked Questions
Q: Does the AAI543-H50/ATA4S-00 support HART communication?
A: Yes. The H suffix identifies the HART digital communication version. It supports HART communication alongside the 4 to 20 mA analog output.
Q: What is the difference between standard and fast switch-over versions?
A: The H50 configuration uses standard switch-over response, with a maximum output drop-below-4 mA period of 100 ms during redundant switchover. The fast-response configuration uses a different suffix code and has a maximum period of 2 ms.
Q: Which terminal block is specified for this configuration?
A: The specified terminal block is ATA4S-00, a pressure clamp terminal block. The corresponding Yokogawa option code is /A4S00. Verify the terminal block and cable arrangement against the installed FIO hardware before replacement.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.