AAI143-H53
Description
Description
The Yokogawa AAI143-H53 is a 16-channel isolated analog input module designed to acquire 4-20 mA DC signals from field transmitters. It supports HART digital communication and provides channel-level signal acquisition for process control systems. This model includes the ISA Standard G3 option and an extended operating temperature specification of -20 to 70 deg C.
Functional Description
The AAI143-H53 receives analog current signals from 2-wire or 4-wire field transmitters and converts them into digital process data for the control system. Its 16 isolated input channels support the acquisition of multiple process variables, such as pressure, flow, level and temperature measurements transmitted as 4-20 mA signals.
The HART communication function allows digital instrument information to be exchanged alongside the analog measurement signal. This provides access to supported smart-transmitter data in addition to the primary process value.
Input Characteristics and Signal Processing
The module uses a 4-20 mA input range with a data update period of 10 ms. Its specified accuracy is +/-16 uA, allowing the control system to process analog measurements at the module's stated accuracy level.
The allowable input current is 24 mA. The transmitter supply provides at least 19.0 V at 20 mA, with a maximum voltage of 25.5 V at 0 mA and an output current limit of 25 mA. These values should be considered when checking the electrical requirements of connected transmitters.
Isolation and Environmental Protection
The input circuitry provides module-level isolation between the field signal circuits and the control system. The specified withstand voltage is 1500 V AC for 1 minute between the input and system sides. Input resistance varies with the operating current, so the voltage drop across the module should be included when checking the transmitter loop's available voltage.
The H53 configuration combines HART communication with the non-explosion-protection version and the ISA Standard G3 option. The G3 option is intended for environments with corrosive gases, while the specified temperature option extends the module's operating range to -20 to 70 deg C.
Model Configuration
The AAI143-H53 suffix codes identify the main hardware configuration:
- H: Digital communication with HART protocol.
- 5: Version without explosion protection.
- 3: ISA Standard G3 option and -20 to 70 deg C temperature option.
These codes describe the module configuration and should be checked against the installed hardware when selecting a replacement.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | AAI143-H53 |
| Brand | Yokogawa |
| Product Type | Analog Input Module |
| Input Signal | 4-20 mA DC |
| Number of Input Channels | 16 |
| Channel Isolation | Isolated between field and system |
| Allowable Input Current | 24 mA |
| Input Resistance (Power ON) | 270 ohm (20 mA) to 350 ohm (4 mA) |
| Input Resistance (Power OFF) | 500 kohm or higher |
| Accuracy | +/-16 uA |
| Data Update Period | 10 ms |
| Transmitter Power Supply | 19.0 V minimum at 20 mA; 25.5 V maximum at 0 mA |
| Transmitter Supply Current Limit | 25 mA |
| Withstand Voltage | 1500 V AC for 1 minute (input to system) |
| HART Communication | Supported |
| Operating Temperature | -20 to 70 deg C |
| Corrosive Gas Protection | ISA Standard G3 |
Frequently Asked Questions
Q: Does the AAI143-H53 support HART communication?
A: Yes. The module supports HART digital communication, allowing compatible field devices to provide additional digital variables alongside their 4-20 mA analog signals. HART communication requires compatible field instruments and system configuration.
Q: Can the module connect to both 2-wire and 4-wire transmitters?
A: The AAI143 hardware supports 2-wire and 4-wire transmitter configurations. The transmitter type is selected for each channel using the module setting pin. Check the actual wiring arrangement and transmitter power requirements before commissioning.
Q: Is the AAI143-H53 suitable for explosive atmospheres?
A: No. The suffix code 5 identifies the version without explosion protection. The ISA Standard G3 option provides corrosive-gas environmental protection, not hazardous-area explosion certification.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.