A2SAM105-H000 S2
Description
Description
The Yokogawa A2SAM105-H000 S2 is a current input/voltage input adaptor designed to interface analog field signals with Yokogawa control system I/O hardware. It supports 4-20 mA DC current signals and 0-10 V DC voltage signals. The -H suffix specifies digital communication using the HART protocol, allowing supported smart field instruments to exchange digital communication over the analog signal loop.
Input Signal and HART Communication
The adaptor accepts current or voltage input signals from field instruments. These two signal types have different electrical characteristics, so the input configuration and field wiring must match the connected transmitter.
The HART communication option allows digital instrument communication alongside the analog process signal. This supports access to compatible field-device information without treating the adaptor as a conventional analog input module with an independently specified channel count.
Electrical Specifications
The input ranges and electrical limits are distinct. The rated ranges define the normal measurement range, while the allowable input limits define the permitted electrical boundaries.
| Parameter | Specification |
|---|---|
| Model | A2SAM105-H000 S2 |
| Brand | Yokogawa |
| Product Type | Current Input/Voltage Input Adaptor |
| Voltage Input Range | 0 to 10 V DC |
| Current Input Range | 4 to 20 mA DC |
| Allowable Input Voltage | 0 to 30 V DC |
| Allowable Input Current | 0 to 25 mA DC |
| Voltage Input Resistance | 1 MOhm (power-on); 100 kOhm or higher (power-off) |
| Current Input Resistance | 320 to 640 Ohm (power-on, depending on input current); 100 kOhm or higher (power-off) |
| Transmitter Power Supply | 15.0 V DC minimum at 20 mA; 24.0 V DC maximum at 0 mA |
| HART Communication | HART 7 |
| Data Update Period | 2 ms for adaptor alone; maximum 10 ms with the I/O module |
| Maximum Current Consumption | 42 mA at 24 V DC; 10 mA at 5 V DC |
| Weight | 0.10 kg |
| Mounting | A2BN3D base plate for adaptor |
| Compatible I/O Module Requirement | A2MMM843 Style 2 or later |
Signal Processing and Accuracy
The adaptor provides separate electrical input characteristics for voltage and current signals. Its input resistance affects the load presented to the field transmitter, particularly in current-loop applications where additional resistance can reduce the available transmitter voltage.
The manufacturer's specified accuracy varies with ambient temperature:
| Input Type | 23 deg C +/- 2 deg C | 0 to 60 deg C | -40 to 70 deg C |
|---|---|---|---|
| Voltage Input | +/-4 mV | +/-8 mV | +/-12 mV |
| Current Input | +/-12 uA | +/-24 uA | +/-40 uA |
The input signal type and measurement range are configured through system software. For current inputs, the transmitter power supply can be configured for 2-wire or 4-wire transmitter connections.
HART Communication and Protection
The -H option provides HART 7 communication for compatible field instruments. This allows the control system to obtain digital instrument information in addition to the conventional 4-20 mA process signal. Up to five HART field devices can be connected through a supported multidrop configuration.
The S2 protection behavior is relevant when diagnosing abnormal current-loop conditions. When overcurrent protection operates, the system does not report an Adaptor Fail alarm to the HIS; instead, the abnormal input condition is detected as IOP (input open). When the adaptor is powered off or overcurrent is detected, the current input loop becomes open.
Model and Suffix Identification
The manufacturer's ordering information identifies the A2SAM105 model and its suffix configuration as follows:
| Code | Description |
|---|---|
| A2SAM105 | Current Input/Voltage Input Adaptor |
| -H | With digital communication (HART protocol) |
| 0 | With no explosion protection |
| 0 | Basic type |
| 0 | Always 0 |
The complete ordering designation A2SAM105-H000 therefore identifies the HART-enabled, non-explosion-protected basic configuration. S2 is retained in the supplied product designation to distinguish the hardware style.
Frequently Asked Questions
Q: Can the A2SAM105-H000 S2 accept both 4-20 mA and 0-10 V DC signals?
A: Yes. It supports both signal types, but the input signal type and range must be configured through the system software to match the connected field instrument.
Q: Does the A2SAM105-H000 S2 support HART communication?
A: Yes. Its -H configuration supports HART 7 communication. Up to five HART field devices can be connected through a supported multidrop arrangement.
Q: What should be checked when replacing an existing A2SAM105-H000 S2?
A: Verify the signal type, transmitter wiring, HART requirements, base plate arrangement and I/O module revision. The adaptor requires an A2MMM843 Style 2 or later when used in the N-IO configuration.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.