A1BR4D-05
Description
Description
The Yokogawa A1BR4D-05 is a terminal board for resistance temperature detector (RTD) input signals in the CENTUM VP Field Control Unit (FIO) system. Based on the A1BR4D model, it provides field signal termination for single or dual-redundant I/O configurations. The -05 ordering code identifies the basic version without explosion protection.
Technical Specifications
| Parameter | Specification |
|---|---|
| Model | A1BR4D-05 |
| Base Model | A1BR4D |
| Brand | Yokogawa |
| Product Type | RTD Input Terminal Board |
| Input Capacity | 16 points x 1 |
| Connected I/O Module | AAR145 |
| Terminal Type | Pressure clamp |
| Mounting Type | DIN rail |
| Weight | 0.30 kg |
Signal Termination and Module Connection
The A1BR4D provides 16 RTD input channels through pressure-clamp terminals. It connects to the Yokogawa AAR145 resistance temperature detector input module using the AKB335 signal cable. The terminal assignments include A, B, and C connections for each channel, supporting the RTD and potentiometer input arrangements specified for AAR145.
For single operation, the I/O module connects through connector CN1. For dual-redundant operation, both CN1 and CN2 are used. The terminal board therefore provides the field wiring interface for the corresponding single or redundant I/O arrangement.
Electrical and Wiring Specifications
- Insulation resistance: 10 Mohm or greater at 200 VDC.
- Withstanding voltage: 200 VAC for 1 minute, between channels.
- Recommended conductor cross-section: 0.5 to 2 mm2 (AWG 20 to 14) without a sleeve.
- Signal cable temperature rating: Ambient temperature plus 10 deg C or higher.
- RTD wiring: The wiring resistance of the IN□A and IN□B signal cables must be identical.
These requirements should be considered when selecting field wiring and preparing the RTD signal connections.
Ordering Code
| Code | Specification |
|---|---|
| A1BR4D | Terminal Board for RTD input |
| -0 | Fixed code; always 0 |
| -5 | Basic type without explosion protection |
The complete ordering number A1BR4D-05 identifies the basic terminal board configuration without explosion protection.
Frequently Asked Questions
Q: Which I/O module is used with the A1BR4D-05?
A: The specified connected module is the Yokogawa AAR145 RTD input module. The corresponding signal cable is AKB335.
Q: Can the A1BR4D-05 support dual-redundant operation?
A: Yes. For dual-redundant I/O configurations, both CN1 and CN2 connectors are used. For single operation, only CN1 is connected.
Q: Does the A1BR4D-05 provide explosion protection?
A: No. The -5 suffix identifies the basic type without explosion protection. It should not be confused with explosion-protected ordering variants.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.