Skip to product information
1 of 3

A1BR4D-05

Brand: Yokogawa
Order Number: A1BR4D-05
Type: RTD Input Terminal Board
Country:
Low stock: 15 left

Description

Caret Down

The Yokogawa A1BR4D-05 is a terminal board for resistance temperature detector (RTD) input signals in the CENTUM VP Field Control Unit (FIO) system. Based on the A1BR4D model, it provides field signal termination for single or dual-redundant I/O configurations. The -05 ordering code identifies the basic version without explosion protection.

Technical Specifications

Parameter Specification
Model A1BR4D-05
Base Model A1BR4D
Brand Yokogawa
Product Type RTD Input Terminal Board
Input Capacity 16 points x 1
Connected I/O Module AAR145
Terminal Type Pressure clamp
Mounting Type DIN rail
Weight 0.30 kg

Signal Termination and Module Connection

The A1BR4D provides 16 RTD input channels through pressure-clamp terminals. It connects to the Yokogawa AAR145 resistance temperature detector input module using the AKB335 signal cable. The terminal assignments include A, B, and C connections for each channel, supporting the RTD and potentiometer input arrangements specified for AAR145.

For single operation, the I/O module connects through connector CN1. For dual-redundant operation, both CN1 and CN2 are used. The terminal board therefore provides the field wiring interface for the corresponding single or redundant I/O arrangement.

Electrical and Wiring Specifications

  • Insulation resistance: 10 Mohm or greater at 200 VDC.
  • Withstanding voltage: 200 VAC for 1 minute, between channels.
  • Recommended conductor cross-section: 0.5 to 2 mm2 (AWG 20 to 14) without a sleeve.
  • Signal cable temperature rating: Ambient temperature plus 10 deg C or higher.
  • RTD wiring: The wiring resistance of the IN□A and IN□B signal cables must be identical.

These requirements should be considered when selecting field wiring and preparing the RTD signal connections.

Ordering Code

Code Specification
A1BR4D Terminal Board for RTD input
-0 Fixed code; always 0
-5 Basic type without explosion protection

The complete ordering number A1BR4D-05 identifies the basic terminal board configuration without explosion protection.

Frequently Asked Questions

Q: Which I/O module is used with the A1BR4D-05?

A: The specified connected module is the Yokogawa AAR145 RTD input module. The corresponding signal cable is AKB335.

Q: Can the A1BR4D-05 support dual-redundant operation?

A: Yes. For dual-redundant I/O configurations, both CN1 and CN2 connectors are used. For single operation, only CN1 is connected.

Q: Does the A1BR4D-05 provide explosion protection?

A: No. The -5 suffix identifies the basic type without explosion protection. It should not be confused with explosion-protected ordering variants.


Product Benefits

Caret Down

Reviews

Caret Down

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)
View full details

Recommended products