3625A
Description
Description
Description
The Triconex 3625A Digital Output Module provides 32 commoned DC outputs with programmable supervision and high current capacity.
Output Configuration
-
Number of Output Signals: 32, commoned
-
Recommended Voltage Range: 16–32 VDC
-
Nominal Voltage: 24 VDC
-
Maximum Voltage: 36 VDC
Power and Current Ratings
-
Logic Power: <13 watts
-
Current Ratings (Maximum): 1.70 ±10% amps per point, 5 amps surge / 7 ms
-
Total Module Output Current: 10 amps per termination panel
-
Minimum Required Load: 10 mA
-
Maximum Output Leakage: 2.0 mA @ 24 VDC, 2.5 mA @ 32 VDC
Protection and Isolation
-
Fuses (Field Termination Module): Not required; output switches are self-protected against over-voltage, over-temperature, and over-current
-
System-to-Field Isolation: 1,500 VDC minimum
Monitoring and Diagnostics
-
Status Indicator (On or Off State): 1 per point
-
Status Indicator (Module Status): Pass, Fault, Load, Active
-
Status Indicator (Field Alarm): Load (1 per point)
-
Point Supervision: Can be programmed per point
-
Short/Open Circuit Detection Threshold: Programmable per supervised point
-
Color Code: Dark Blue
Product Benefits