TM3AQ2
Description
Description
Configured for analog current and voltage signal generation in Modicon TM3 expansion I/O systems, the Schneider Electric TM3AQ2 (TM3AQ2 Analog Output Module) provides two configurable outputs for Modicon M221, M241, M251 and M262 controllers. It supports 4-20 mA, 0-20 mA, 0-10 V and -10 to 10 V signals through removable screw terminals.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | TM3AQ2 |
| Brand | Schneider Electric |
| Series | Modicon TM3 |
| Product Type | Analog Output Module |
| Analog Outputs | 2 |
| Compatible Controllers | Modicon M221, M241, M251, M262 |
| Output Types | 4-20 mA, 0-20 mA, 0-10 V, -10 to 10 V |
| Resolution | 12 bits; 11 bits + sign |
| Stabilization Time | 1 ms |
| Conversion Time | 1 ms + 1 ms per channel + 1 controller cycle time |
| Absolute Accuracy | +/- 0.1 %FS at 25 deg C; +/- 1 %FS |
| Repeat Accuracy | +/- 0.4 %FS |
| Output Ripple | 20 mV |
| Cross Talk | <= 1 LSB |
| Voltage Load Impedance | 1 kOhm |
| Current Load Impedance | 300 Ohm |
| Insulation | 1500 V AC output-to-supply; 500 V AC output-to-internal logic |
| Supply Voltage | 24 VDC |
| Current Consumption | 70 mA at 24 VDC, full load |
| No-Load Consumption | 30 mA at 24 VDC; 35 mA at 5 VDC |
| Electrical Connection | Removable screw terminal block, 5.08 mm pitch |
| Cable Type | Twisted shielded pairs, output cable < 30 m |
| Mounting | TH35-15 or TH35-7.5 DIN rail; plate or panel with fixing kit |
| Dimensions | 23.6 mm W x 70 mm D x 90 mm H |
| Weight | 0.115 kg |
| Operating Temp | -10 to 55 deg C horizontal; -10 to 35 deg C vertical |
| Storage Temp | -25 to 70 deg C |
| Protection Rating | IP20 |
| Humidity | 10-95 % RH, non-condensing |
| Operating Altitude | 0-2000 m |
| Standards | IEC 61131-2 |
| Certifications | CE, UKCA, RCM, EAC, cULus, cULus HazLoc |
| Origin | Japan |
| Lifecycle Carbon Footprint | 42 kg CO2 eq. |
TM3 Analog Output Signal Characteristics
The TM3AQ2 converts controller commands into two analog output channels. Each channel can be configured for current or voltage operation. The listed LSB values are 2.44 mV for 0-10 V, 4.88 mV for -10 to 10 V, 4.88 uA for 0-20 mA and 3.91 uA for 4-20 mA.
Output-to-supply insulation is rated at 1500 V AC, while output-to-internal-logic insulation is rated at 500 V AC. The module specifies +/- 0.01 %FS non-linearity and a temperature drift of +/- 0.006 %FS/deg C.
The TM3 expansion assembly distributes data and power through the bus expansion connector. The module uses a simple interlocking assembly mechanism for connection with compatible Modicon TM3 components.
Frequently Asked Questions
Q: What output signals does the TM3AQ2 provide?
A: The module provides two analog outputs configurable for 4-20 mA, 0-20 mA, 0-10 V or -10 to 10 V operation.
Q: What load impedance is specified for the outputs?
A: The specified load impedance is 1 kOhm for voltage outputs and 300 Ohm for current outputs.
Q: What is the 24 VDC current consumption at full load?
A: The specified typical current consumption is 70 mA at 24 VDC with the outputs at full load.
Field Installation Guidelines
- Install the module on a TH35-15 or TH35-7.5 DIN rail conforming to IEC 60715, or use the specified plate/panel fixing kit.
- Use the removable screw terminal block for supply and output wiring.
- Use twisted shielded pairs for analog output wiring and keep output cables below the specified 30 m maximum length.
- Separate analog signal wiring from high-current and high-switching power conductors where practical to reduce electromagnetic coupling.
- Connect cable shields according to the control panel grounding design and maintain a consistent shielding method across the analog signal path.
- Verify the selected output mode against the receiving device input type before energizing the circuit.
- Observe the specified 1 kOhm maximum voltage-output load impedance and 300 Ohm maximum current-output load impedance.
- Confirm the controller and TM3 expansion configuration before commissioning. The module is compatible with Modicon M221, M241, M251 and M262 controllers.
- Maintain the specified ambient temperature limits according to horizontal or vertical installation orientation.
- Allow sufficient panel clearance for terminal access and module removal without applying mechanical force to the bus interconnection.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.