Skip to product information
1 of 3

MNB1000-15

Brand: Schneider
Order Number: MNB1000-15
Type: Remote I/O Expansion Module
Country:
Low stock: 17 left

Description

Caret Down

Configured for remote input and output point expansion in the TAC I/A Series MicroNet BACnet Plant Controller network, the Schneider Electric MNB1000-15 (MNB1000-15 Remote I/O Expansion Module) provides direct physical signal acquisition and output execution through 15 dedicated I/O channels.

Hardware Specifications

Parameter Specification
Model MNB1000-15
Brand Schneider Electric
Series TAC I/A Series MicroNet BACnet
Weight 0.45 kg
Dimensions 100 mm x 178 mm x 56 mm
Operating Temp -40 to 60 deg C
Power Consumption 16 VA at 24 VAC
Power Supply 20.4 to 30 VAC, 50/60 Hz, nominal 24 VAC
I/O Capacity 15 points total
Universal Inputs 6 channels
Universal Outputs 3 channels
Digital Outputs 6 Triac outputs
Remote I/O Bus Dedicated remote I/O bus with DIP-switch addressing
Mounting Type Panel mount / wall mount
Input Signal Types 10k Ohm thermistor, RTD, 0-5 VDC, 0-20 mA, dry contact, pulse input
Universal Output Range 0-20 mA and 0-10 VDC
Triac Output Rating 12 VA at 24 VAC, 50/60 Hz, individually isolated
Certifications UL 916, FCC Part 15 Class A, CE Mark, C-Tick

Profinet / EtherNet-IP Deterministic Networks and I/O Density Scaling

The MNB1000-15 performs local point expansion through the TAC I/A Series MicroNet BACnet architecture. The module increases controller capacity by adding six Universal Inputs, three Universal Outputs, and six Triac Digital Outputs. A single MNB-1000 controller can support up to eight MNB1000-15 expansion modules, providing a maximum system capacity of 152 I/O points.

The hardware uses removable electronics with screw terminal connections for field wiring access. DIP-switch addressing defines the remote I/O position, while LED indicators provide status information for power, communication, and output activity.

Frequently Asked Questions

Q: What physical signals can the MNB1000-15 Universal Inputs accept?
A: The six Universal Inputs support thermistor signals, RTD inputs, 0-5 VDC analog voltage, 0-20 mA analog current with external shunt resistance, dry contact switching, and pulse input signals.

Q: How are the Triac Digital Outputs electrically configured?
A: The six Triac Digital Outputs provide individually isolated outputs rated at 12 VA at 24 VAC, 50/60 Hz.

Q: What installation interface is provided for field wiring?
A: The module uses fixed and removable screw terminals designed for AWG #14 to #18 wiring connections.

Field Installation Guidelines

Install the MNB1000-15 on a suitable panel or wall-mounted surface according to the MicroNet BACnet controller installation requirements. Verify the 24 VAC power source polarity and wiring separation before energizing the module.

Use dedicated field wiring paths for input signals, analog outputs, and Triac outputs to reduce electrical interference. Shielded cables should be applied where signal noise conditions require additional protection, with cable shields terminated according to site grounding practices.

Confirm DIP-switch addressing before connecting the remote I/O bus. Ensure removable terminal blocks are fully seated and verify LED status indicators after power application.