Skip to product information
1 of 3

PM5110

Brand: Schneider
Order Number: PM5110
Type: Power Meter
Country:
Low stock: 17 left

Description

Caret Down

Configured for electrical energy measurement and Modbus communication in PowerLogic PM5000 monitoring systems, the Schneider Electric METSEPM5110 (PM5110 Power Meter) provides direct measurement of voltage, current, frequency, power factor, energy, active power, reactive power, and harmonic data through RS485 Modbus interfaces.

Hardware Specifications

Parameter Specification
Model METSEPM5110
Brand Schneider Electric
Series PowerLogic PM5000
Product Type Power Meter
Weight 380 g
Dimensions 96 mm W x 72 mm D x 96 mm H
Operating Temp -25 to 70 deg C
Power Consumption 11 VA maximum at 415 VAC
Display Type Monochrome graphic LCD, 128 x 128 pixels
Mounting Type Flush-mounted
Measurement Network 1P + N, 3P + N, 3P
Rated Supply Voltage 90-450 VAC, 45-65 Hz / 100-300 VDC
Line Rated Current 1 A or 5 A
Measurement Voltage 35-760 VAC phase-to-phase / 20-440 VAC phase-to-neutral
Measurement Frequency 45-65 Hz
Sampling Rate 64 samples/cycle
Power Quality Measurement Up to 15th harmonic
Energy Accuracy Class Class 0.5S IEC 62053-22
Digital Output 1 digital pulse output
Alarm Configuration 33 configurable alarms
Communication Protocol Modbus RTU, Modbus ASCII, JBUS
Communication Interface RS485, 2-wire
Baud Rate 9.6, 19.2, 38.4 kbaud
Protection Rating IP54 front display, IP30 rear
Certifications CE, cULus, IEC 61010-1, IEC 62053-22

Modbus RS485 and Power Quality Measurement

The METSEPM5110 integrates electrical parameter acquisition with RS485 serial communication using Modbus RTU and ASCII protocols. The measurement engine samples electrical waveforms at 64 samples per cycle and records voltage, current, frequency, power factor, active and reactive power, and energy values. Harmonic analysis supports measurement up to the 15th harmonic for power quality evaluation.

The meter supports single-phase and three-phase network configurations with current transformer inputs rated at 1 A or 5 A. The RS485 communication port provides two-wire data transmission with configurable baud rates and supports remote monitoring through Modbus-based control systems.

Frequently Asked Questions

Q: What communication interface is available on the METSEPM5110?
A: The meter provides an RS485 two-wire communication interface supporting Modbus RTU, Modbus ASCII, and JBUS protocols.

Q: What type of electrical measurements can the PM5110 perform?
A: The PM5110 measures voltage, current, frequency, power factor, energy, active power, reactive power, and harmonic values up to the 15th harmonic.

Q: Does the METSEPM5110 support digital output functions?
A: Yes. The meter includes one digital pulse output and supports 33 configurable alarm functions.

Field Installation Guidelines

Install the METSEPM5110 in a suitable flush-mount panel opening with correct terminal assignment for voltage circuits, current transformer inputs, control circuits, digital output circuits, and RS485 communication wiring.

Use shielded twisted-pair cable for RS485 communication where required by the installation environment. Connect cable shields according to the site grounding practice to reduce electromagnetic interference. Keep communication wiring separated from high-current power conductors to minimize electrical noise coupling.

Verify the phase sequence, current transformer polarity, rated voltage range, and network configuration before energizing the meter. Confirm Modbus addressing, baud rate, and communication parameters before integrating the device into a monitoring network.