Configured for electrical energy measurement and power quality monitoring in PowerLogic PM5000 platforms, the Schneider Electric METSEPM5100 (PM5100 Power Meter) provides direct measurement of voltage, current, frequency, power factor, active/reactive power, energy values, and harmonic components up to the 15th order.

Hardware Specifications

Parameter Specification
Model METSEPM5100
Brand Schneider Electric
Product Series PowerLogic PM5000
Product Type Power Meter
Weight 380 g
Dimensions 96 mm W x 72 mm D x 96 mm H
Operating Temp -25 to 70 deg C (meter); -20 to 70 deg C (display)
Power Consumption 11 VA maximum at 415 VAC
Display Type Monochrome graphic LCD, 128 x 128 pixels
Mounting Mode Flush-mounted
Rated Supply Voltage 90 to 450 VAC, 45 to 65 Hz; 100 to 300 VDC
Rated Current Input 1 A or 5 A
Network Configuration 1P + N, 3P, 3P + N
Measurement Voltage 35 to 760 VAC between phases; 20 to 400 VAC between phase and neutral
Frequency Range 45 to 65 Hz
Sampling Rate 64 samples/cycle
Harmonic Measurement Up to 15th harmonic
Accuracy Class Class 0.5S active energy according to IEC 62053-22
Pulse Output 1 energy pulse output
Alarm Function 33 configurable alarms
Protection Rating IP54 front display, IP30 rear enclosure
Certifications CE, cULus

Deterministic Network and Power Measurement Characteristics

The METSEPM5100 integrates electrical acquisition circuits for three-phase and single-phase power monitoring. The measurement engine processes voltage and current input signals with 64 samples per cycle and calculates active power, reactive power, apparent power, energy, frequency, and power factor values.

The meter supports power quality analysis through harmonic measurement up to the 15th harmonic component. Measurement accuracy is defined by IEC 62053-22 Class 0.5S requirements for active energy.

The device includes a pulse output channel for remote energy accumulation and provides configurable alarm handling with 33 alarm conditions. Recorded data includes minimum and maximum instantaneous values with time stamping functions.

Frequently Asked Questions

Q: What current input signals are supported by the METSEPM5100?
A: The meter accepts line current inputs rated at 1 A or 5 A for current transformer measurement circuits.

Q: Does the METSEPM5100 provide serial communication ports?
A: The METSEPM5100 model provides pulse output communication only. No communication protocol is assigned for the communication port.

Q: What mounting method is required for installation?
A: The meter is installed using a flush-mounted configuration with a framework mounting support.

Field Installation Guidelines

Install the METSEPM5100 in a panel cutout suitable for the 96 mm x 96 mm front display format. Connect voltage sensing circuits, current transformer inputs, and pulse output wiring according to the terminal assignment documentation.

Current transformer secondary wiring should maintain correct polarity and avoid open-circuit operation during commissioning. Separate measurement wiring from high-voltage switching conductors where possible to reduce electrical interference.

Protect signal wiring with proper grounding and shielding practices according to the installation environment. Verify phase sequence, network configuration, and rated input settings before energizing the meter.