Skip to product information
1 of 3

ABL4RSM24200

Brand: Schneider
Order Number: ABL4RSM24200
Type: Regulated Switch Mode Power Supply
Country:
Low stock: 17 left

Description

Caret Down

Configured for regulated 24 VDC power conversion within Modicon Power Supply architectures, the Schneider Electric ABL4RSM24200 (ABL4RSM24200 regulated switch mode power supply) accepts single-phase or two-phase AC input and delivers 20 A DC output.

Hardware Specifications

Parameter Specification
Model ABL4RSM24200
Brand Schneider Electric
Product Type Regulated switch mode power supply
Product Range Modicon Power Supply
Input Voltage 120...230 V AC phase-to-phase; 120...230 V AC single phase; 300...370 V DC
Rated Power 480 W
Output Voltage 24 V DC
Output Current 20 A
Temporary Current Boost 1.5 x In for 5 s
Inrush Current 35 A
Power Factor 0.75 at 24 V DC
Efficiency 90% at 120 V AC; 92% at 230 V AC
Output Voltage Adjustment 100...116% adjustable
Power Dissipation 55 W; 43 W
Current Consumption 4.4 A at 230 V AC; 8.4 A at 120 V AC
Output Protection Short-circuit, overload, thermal, and overvoltage protection
Output Coupling Redundant parallel with internal diode; series connection
Status Indication Green LED for output voltage; red LED for overload, overtemperature, or overvoltage
Dimensions 80 mm W x 127 mm H x 139 mm D
Weight 1.3 kg
Operating Temperature Not specified in supplied documentation
Power Consumption Input consumption: 4.4 A at 230 V AC; 8.4 A at 120 V AC
Terminals Screw terminals, 0.5...4 mm2 conductors depending on connection
Mounting 35 x 15 mm or 35 x 7.5 mm symmetrical DIN rail
Mounting Position Vertical
Protection Degree IP20
Safety Supply SELV according to IEC 60950-1, IEC 60204-1, and IEC 60364-4-41
Standards CULus 508; EN/IEC 62368-1
Certifications CSA C22-2 No 14; CULus 508
EMC EN 50081-1, EN 50082-2, IEC 61000-6-2
Marking CE

Regulated Output and Redundant Power Architecture

The ABL4RSM24200 uses regulated switch mode conversion to provide a nominal 24 V DC output at 20 A. The output voltage is adjustable from 100% to 116% of nominal.

The power supply supports redundant parallel operation through an internal diode arrangement. Series connection is also specified for the output circuit.

Protection functions include automatic-reset short-circuit protection, overload protection, thermal protection, and overvoltage protection. The temporary output current capability reaches 1.5 x rated current for 5 seconds.

The status indication separates normal output voltage from overload, overtemperature, and overvoltage conditions through dedicated green and red LEDs.

Frequently Asked Questions

Q: What input configurations does the ABL4RSM24200 support?
A: The unit accepts 120...230 V AC phase-to-phase, 120...230 V AC single-phase, or 300...370 V DC input.

Q: Can the ABL4RSM24200 operate in a redundant power configuration?
A: Yes. The specified output coupling supports redundant parallel operation using an internal diode, as well as series connection.

Q: What mounting arrangement is specified for this power supply?
A: The unit mounts vertically on either 35 x 15 mm or 35 x 7.5 mm symmetrical DIN rail.

Field Installation Guidelines

Install the power supply vertically on a compatible symmetrical DIN rail and maintain clearances required by the installation enclosure.

Verify the selected input terminals before energization because the unit provides separate connection arrangements for single-phase and phase-to-phase AC input.

Use the specified screw-terminal conductor ranges and tighten all terminals according to the applicable installation documentation.

Route AC input wiring separately from low-voltage DC signal wiring where practical to reduce conducted and radiated interference.

Connect the protective earth terminal according to the enclosure grounding scheme and applicable electrical installation standards.

For redundant parallel operation, verify the power-system topology and polarity before connecting the output conductors.

Do not bypass the specified short-circuit, overload, thermal, or overvoltage protection circuits during commissioning.

The product is discontinued, with discontinuation dated 31 Dec 2013 and end-of-service dated 25 Sept 2025. The supplied Schneider Electric documentation identifies ABL8RPM24200 as the recommended replacement.