ABE7R16T330
Description
Description
The Schneider Electric ABE7R16T330, also cataloged as the ABE7R16T330 Sub-base with Plug-in Electromechanical Relay, operates as a dedicated hardware component for field signal interface distribution and isolation within Modicon Telefast PLC I/O system platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | ABE7R16T330 |
| Brand | Schneider Electric |
| Origin | France |
| Weight | 1.3 kg |
| Dimensions | 8.60 x 10.00 x 29.20 cm |
| Operating Temp | -5 to 60 deg C |
| Storage Temp | -40 to 80 deg C |
| Power Consumption | Max supply current 1 A |
| Rated Supply Voltage | 19 to 30 VDC |
| Channel Density | 16 channels |
| Contact Composition | 1 C/O per channel |
| Short-Circuit Protection | 1 A fast blow internal fuse (5 x 20 mm) |
| Rated Insulation Voltage | 2000 V terminals to mounting rail, 300 V coil to contact |
| Enclosure Rating | IP2X |
| Relay Compatibility | ABR7S33 / ABR7S11 / ABR7S21 / ABR7S23 |
Deterministic I/O Bus & Backplane Connectivity
The ABE7R16T330 interface unit provides fixed point-to-point electrical routing via HE10 pre-wired connectors to scale high-density I/O signals directly from controller hardware cards. Channel-to-channel isolation safeguards the primary control electronics, ensuring firmware execution on the master PLC process card is isolated from field surges or electrical fault transience up to 2.5 kV impulse withstand thresholds.
Frequently Asked Questions
Q: What is the primary short-circuit protective element used on the power input side?
A: Protection is supplied via an internal 1 A fast blow fuse measuring 5 x 20 mm on the PLC termination side.
Q: What mounting configurations are permitted for field installation?
A: The module attaches directly via integrated retention clips onto standard 35 mm symmetrical DIN rails or mounts to a solid enclosure backplate via a dedicated screw fixing kit.
Field Installation Guidelines
- Mount the unit on standard 35 mm symmetrical DIN rails or secure it directly to a grounded metal sub-panel with fixing screws.
- Ensure wiring screw terminals are torqued strictly to 0.6 N.m using a flat 3.5 mm screwdriver.
- Route HE10 ribbon connectors from the PLC I/O card directly to the sub-base, maintaining safe clearance from high-voltage AC lines.
- Verify that ground connections are tied cleanly to earth to provide maximum immunity against electromagnetic fields up to 10 V/m.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...