ABE7R16S210
Description
Description
Configured for discrete signal interface adaptation in PLC I/O systems, the Schneider Electric ABE7R16S210 (ABE7R16S210 Electromechanical Relay Sub-Base) provides direct physical/electrical execution.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | ABE7R16S210 |
| Brand | Schneider Electric |
| Origin | France |
| Weight | 0.405 kg |
| Dimensions | 206 mm (Width) |
| Operating Temp | -5 to 60 deg C |
| Power Consumption | 0.36 W per channel max (PLC end) |
| Number of Channels | 16 |
| Rated Supply Voltage | 24 VDC |
| Max Switching Voltage | 250 VAC (50/60 Hz), 30 VDC |
| Max Current per Channel | 5 A (pre-actuator end) |
| Max Output Common Current | 10 A |
| Contact Type | 1 NO per channel |
| Insulation Voltage (Ui) | 2000 V |
| Impulse Withstand Voltage | 2.5 kV |
| IP Protection Rating | IP2X |
| Mounting Type | 35 mm DIN rail or screw panel mount |
Deterministic Network and Backplane I/O Density Scaling
The ABE7R16S210 provides high-density signal consolidation between field devices and host controllers across PLC platforms. Pre-wired system connections via HE10 connectors maintain signal integrity while streamlining backplane bus communication pathways. Channel-to-channel isolation and structured physical interfaces minimize signal cross-talk, permitting deterministic signal routing with low latency across local and distributed I/O racks.
Frequently Asked Questions
Q: What is the maximum switching time for the onboard NO relay contacts?
A: The operating time is less than or equal to 10 ms for coil energization and NO contact closure, and less than or equal to 5 ms for coil de-energization and NO contact opening.
Q: What screw torque specification is required for wiring terminals?
A: Wiring terminals require a tightening torque of 0.6 N.m using a 3.5 mm flat screwdriver to ensure secure electrical contact and prevent terminal damage.
Field Installation Guidelines
Mount the sub-base horizontally on a standard 35 mm symmetrical DIN rail using integrated retaining clips or secure directly to a mounting plate with fixing screws. Maintain minimum clearance above and below the unit to ensure natural convection cooling. Ensure all 24 VDC power feed connections follow correct polarity. Ground the pre-wired cable shielding according to standard industrial noise suppression procedures to prevent transient interference on digital I/O lines.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.