Skip to product information
1 of 3

1756-OF8H

Brand: Allen-Bradley
Order Number: 1756-OF8H
Type: Analog Output Module
Country: USA
1000 in stock

Description

Caret Down

Overview

1756-OF8H is an 8-channel HART-enabled analog output module from Allen-Bradley, designed for precise voltage and current output control with integrated HART communication in ControlLogix systems.

General Information

  • Manufacturer: Allen-Bradley (Rockwell Automation)

  • Series: ControlLogix

  • Module Type: HART Analog Output Module

  • Channels: 8 voltage or current outputs

  • HART Support: 1 modem per module

  • Isolation: None (single-ended)

  • Electrical Connection: Screw/spring clamp (copper wire)

  • Wire Category: 2 (signal ports)

  • Terminal Block: 1756-TBNH, torque 1.36 Nm (12 in-lb)

  • Module Keying: Electronic, software configurable

Electrical Specifications

  • Output Ranges: −10…+10 V, 0…20 mA, 4…20 mA

  • Output Signal: ±10.4 V, 0–20 mA, 4–20 mA

  • Load Reactance: Voltage: 1 µF, Current: 10 µH

  • Resolution: 15–16 bit for all ranges

  • Output Conversion: R-Ladder DAC, monotonic

  • Input Conversion: Successive approximation

  • Data Format: Integer mode (2’s complement, left-justified), IEEE 32-bit floating point

  • Offset Drift: 100 µV/°C, 200 nA/°C

  • Gain Drift: Voltage: 20 ppm/°C, Current: 35 ppm/°C

  • Module Error: Voltage: 0.15% of range, Current: 0.3% of range

  • Overvoltage Protection: ±24 V DC

Performance

  • Settling Time:

    • Current (no HART): <23 ms to 95% with resistive loads

    • Current (with HART): <37 ms to 95% with resistive loads

    • Voltage: <8.5 ms to 95% with resistive loads

Power Requirements

  • Backplane Current: 5.1 V DC @ 230 mA, 24 V DC @ 230 mA

  • Total Backplane Power: 6.54 W

  • Power Dissipation: 4.92 W

  • Thermal Dissipation: 16.78 BTU/h

  • Slot Width: 1

Environmental Conditions

  • Operating Temperature: 0…+60 °C (32…140 °F)

  • Non-Operating Temperature: −40 °C

  • Relative Humidity: 5–95% non-condensing

  • Vibration: 2 G @ 10…500 Hz

  • Shock: 30 G operating, 50 G non-operating

Immunity & Protection

  • ESD Immunity: 6 kV (contact), 8 kV (air)

  • EFT/B Immunity: ±2 kV @ 5 kHz on signal ports

  • Conducted RF Immunity: 10 V rms, 1 kHz sine-wave, 80% AM from 150 kHz–80 MHz

  • Surge Protection: ±2 kV line-earth (CM) on shielded ports


Product Benefits

Caret Down

Reviews

Caret Down

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)
View full details

Recommended products