MVI56-PDPMV1
Description
Description
Overview
-
Model: MVI56-PDPMV1
-
Type: PROFIBUS DPV1 Master Communication Module
-
Application: Provides PROFIBUS DPV1 master connectivity for ControlLogix systems, enabling integration with PROFIBUS slave devices
Electrical & Mechanical Characteristics
-
Backplane Current Load:
-
800 mA @ 5 V DC
-
3 mA @ 24 V DC
-
-
Operating Temperature: 0 … 60 °C (32 … 140 °F)
-
Storage Temperature: –40 … 85 °C (–40 … 185 °F)
-
Shock Resistance: 30 G operational, 50 G non‑operational
-
Vibration Resistance: 5 G @ 10 … 150 Hz
-
Relative Humidity: 5 … 95% (non‑condensing)
Indicators & Diagnostics
-
LED Indicators:
-
Module status
-
Backplane transfer status
-
Application status
-
Serial activity and error status
-
-
Debug/Configuration Port (CFG): RJ45 (DB‑9M with supplied cable), RS‑232 only
-
Ethernet Routing: CIPConnect® via 1756‑ENBT, 1756‑EN2T or similar
PROFIBUS DPV1 Master Specifications
-
Protocol Role: PROFIBUS DPV1 Master
-
Integration: Supports communication with multiple PROFIBUS slave devices
-
Configuration: GSD file support for device integration
Shipped Accessories
-
RJ45 to DB‑9M cables for each port
-