MTL5074
Description
Description
Description
MTL5074 is a single-channel temperature converter from Eaton MTL for THC or RTD inputs, suitable for hazardous areas.
Input Characteristics
-
Signal Source: THC types J, K, T, E, R, S, B, N; 2/3/4-wire platinum RTDs (100 Ω at 0°C)
-
Input Range: –75 to +75 mV or 0–400 Ω
-
Input Span: 3–150 mV or 10–400 Ω
-
RTD Excitation: 200 µA nominal
-
Cold Junction Compensation: Automatic or selectable, error ≤1.0°C
-
Common Mode Rejection: 120 dB for 240V (50/60 Hz)
-
Series Mode Rejection: 40 dB
Accuracy & Drift
-
Calibration Accuracy: ±15 µV / ±0.05% (THC), ±80 mΩ (RTD), Output ±11 µA
-
Temperature Drift: ±0.003%/°C (THC), ±7 mΩ/°C (RTD), Output ±0.6 µA/°C
Output & Power
-
Output Range: 4–20 mA nominal, direct or reverse
-
Max Load Resistance: 600 Ω
-
LED Indicator: Green for power/status
-
Power Consumption: 68 mA at 24V, 82 mA at 20V, 52 mA at 35V
-
Power Dissipation: 1.5 W at 24V, 1.6 W at 35V
Safety & Isolation
-
Isolation: 250 V AC between safe and hazardous circuits
-
Safety Drive on Sensor Burnout: Upscale, downscale, or off
-
Safety Ratings: Terminals 1–3: Vout 1.1–6.6 V, Iout 7–76 mA, Pout ≤0.13 W depending on configuration
Configuration
-
Standard Setup: RTD 3-wire, linearisation enabled, CJ disabled, °C units, 0 s damping
-
Alarms: Open circuit high, transmitter failure low, CJ failure low
-
Configurator: PC with MTL PCS45 software and PCL45 interface
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews

Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.