MTL4016 is a dual-channel interface unit for switches and proximity detectors, designed for hazardous locations.
Channel & Location Ratings
-
Number of Channels: Two
-
Switch Location: Zone 0, IIC, T6 hazardous area; Div.1, Group A
-
Proximity Detector Location: Zone 0, IIC, T4–6 if certified; Div.1, Group A
Sensor & Signal Characteristics
-
Voltage to Sensor: 7.0–9.0 V DC from 1kΩ
-
Output Behavior:
• Closed if >2.1 mA (<2 kΩ)
• Open if <1.2 mA (>10 kΩ) -
Hysteresis: 200 µA (650 Ω) nominal
-
Phase Reversal: Independent switches for each channel
Fault Detection & Protection
-
Line Fault Detection (LFD): Outputs open if input current <100 µA (broken) or >6.5 mA (short)
-
Earth Fault Protection: ‘No-fail’ with MTL4220 leakage detector connected to terminals 3 & 6
-
Fault Handling: Fault on any line triggers output but unit remains operational
Relay Output
-
Type: Double-pole on/off, open when de-energized
-
Response Time: max 2 ms
-
Contact Rating: 10 W, 0.5 A, 35 V DC
-
Contact Life: 1 million operations max load
Indicators
-
Channel LED: Amber, ON when output closed
-
Power LED: Green
Power Consumption
-
Current:
• 50 mA at 24 V DC
• 60 mA at 20 V DC
• 45 mA at 35 V DC -
Power Dissipation:
• 1.2 W at 24 V
• 1.6 W at 35 V
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews



Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.