MTL5046
Description
Description
Description
MTL 5046 Isolating Driver with one channel for hazardous area applications.
Channel & Location
-
Channels: 1
-
Load Location: Zone 0 IIC T4–6, Div.1 Group A (if certified)
Input (Safe Area)
-
Signal Range: 4–20 mA
-
Under/Over Range: 1–24 mA
-
Input Voltage Drop: <4 V @ 20 mA
-
Ripple: <40 µA peak-to-peak
Output (Hazardous Area)
-
Load Resistance: 100–800 Ω (16 V @ 20 mA)
-
Output Resistance: >2 MΩ
-
Bandwidth: 500 Hz–10 kHz
-
Transfer Accuracy: <10 µA @ 20°C
-
Response Time: ≤100 µs to 10% final value
Stability
-
Temp Drift: <0.5 µA/°C
Diagnostics
-
Line Fault Detection: Impedance >100 kΩ between pins 11 & 12
-
LED Indicator: Green = Power
Power
-
Supply Voltage: 20–35 VDC
-
Max Current: 65 mA @ 24 V, 75 mA @ 20 V, 50 mA @ 35 V
-
Power Dissipation: 1.5 W @ 24 V, 1.6 W @ 35 V
Safety
-
Rating: 28 V, 300 Ω, 93 mA
-
Um: 250 V rms or DC