XCL5010
Description
Description
Configured for programmable building automation and distributed HVAC control, the Honeywell XCL5010 (XCL5010 Direct Digital Controller) executes control logic and exchanges data through LONWORKS and C-bus communication networks. The controller supports modular Distributed I/O expansion, energy management functions, alarm and trend processing, and remote communication through a modem or ISDN terminal adapter at up to 38.4 Kbaud.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | XCL5010 |
| Brand | Honeywell |
| Product Series | Excel 500 |
| Product Type | Direct Digital Controller |
| Weight | 1.26 lbs |
| Supply Voltage | 24 VAC |
| Programming | Freely programmable using Honeywell CARE |
| Program Storage | Flash EPROM |
| Network Interface | LONWORKS |
| Controller Communication | C-bus; supports communication between up to 30 Excel 500 controllers |
| LONWORKS Network Variables | Up to 512 NVs |
| Physical Data Points | 128 per controller in C-bus configuration |
| Pseudo Data Points | 256 per controller in C-bus configuration |
| Distributed I/O Expansion | Up to 16 modules per controller in C-bus configuration |
| Networked I/O Capacity | Typically 190 physical inputs/outputs via network variables in a LONWORKS network |
| Remote Communication | Modem or ISDN terminal adapter, up to 38.4 Kbaud |
| Energy Management Functions | Optimum start/stop, night purge, maximum load demand |
| Mounting | DIN rail |
| Internal Power Supply | Integrated power supply module |
LONWORKS Network Integration and Control Functions
The XCL5010 supports open LONWORKS networks and LONMARK compliance for interoperability with compatible Honeywell and third-party devices. Network integration includes Excel 500, Excel 10, and Excel 50 controllers, together with Distributed I/O modules.
- Network variable management: NVBooster reduces the number of required network variables, while the controller supports up to 512 NVs for LONWORKS integration.
- Binding recovery: Network variable bindings can be restored following a controller reset, reducing the need to repeat binding configuration after controller replacement.
- Distributed I/O integration: Automatic binding between the CPU and Honeywell Distributed I/O modules reduces manual network variable configuration.
- Controller communication: C-bus supports communication between up to 30 Excel 500 controllers.
- Program management: Applications are developed with Honeywell CARE and downloaded to Flash EPROM. Firmware downloading is supported through modem and C-bus communication.
- Monitoring functions: Alarm processing, trend functions, global broadcast hysteresis, and network-wide time synchronization are supported.
Frequently Asked Questions (FAQ)
Q: Which communication interfaces are supported by the XCL5010?
A: The controller supports LONWORKS network integration, C-bus communication, and modem or ISDN terminal adapter connections. The documented modem or ISDN transmission rate is up to 38.4 Kbaud. GSM wireless and dial-up communication through TCP/IP networks are also listed among the Excel 500 communication options.
Q: How many Distributed I/O modules can one XCL5010 controller support?
A: In the C-bus configuration, one Excel 500 controller supports up to 16 Distributed I/O modules, 128 physical data points, and 256 pseudo data points. The separate LONWORKS network configuration can typically control 190 physical inputs/outputs through network variables.
Q: How are control applications loaded into the XCL5010?
A: Applications are programmed using Honeywell CARE and downloaded into Flash EPROM. The Excel 500 system also supports firmware downloading through modem and C-bus communication.
Field Installation Guidelines
- Mounting: Install the controller on a compatible DIN rail inside a control cabinet. Secure the assembly and maintain access to the terminal connections.
- Power supply: Verify the 24 VAC supply against the controller's applicable hardware documentation. The Excel 500 documentation specifies a shared transformer arrangement for the CPU and connected Distributed I/O modules.
- Network wiring: Connect LONWORKS and C-bus wiring according to the applicable interface specifications. Confirm network topology and device compatibility before commissioning.
- Signal segregation: Route low-voltage control wiring separately from power conductors where required by the installation standards. Avoid routing communication cables alongside sources of electrical interference.
- Grounding and shielding: Apply the grounding and cable-shield termination practices specified for the selected communication interface. Do not assume identical shield termination requirements for LONWORKS and C-bus.
- Configuration: Load the correct CARE application and verify data point assignments, network variable bindings, controller addressing, and Distributed I/O communication.
- Commissioning: Confirm power status, controller communication, I/O response, alarm operation, and time synchronization before releasing the system for automatic control.
- Environmental verification: Confirm the permitted operating temperature and cabinet conditions using the applicable Honeywell installation documentation, as these values are not included in the supplied product data.
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...