FTA-T-14
Description
Description
Overview
The FTA-T-14 is a Fail-Safe 0(4)-20 mA Analog Input module from Honeywell, designed for precise monitoring of analog signals in industrial control systems.
Channels & Input
-
Number of Input Channels: 16 (2 groups of 8 with common 0 V)
-
Input Current: 0 to 25 mA
-
Input Resistance: 250 Ω (±1%)
-
Power Requirement: 30 VDC, 3 mA (without input loop loads)
Output
-
To Passive Transmitters (Vext):
-
Output Resistance: 270 Ω (±5%)
-
Igniting Current per Channel: <120 mA at 30 VDC
-
To 10105/2/1 Module:
-
Output Voltage: 0 to 4 VDC
Physical Specifications
-
Module Dimensions: 200 × 70 × 60 mm (7.87 × 2.76 × 2.36 in)
-
DIN Rail: TS32 / TS35 × 7.5 mm, used rail length 201 mm (7.91 in)
-
Termination: Screw terminals
-
Max Wire Diameter: 2.5 mm² (AWG 14)
-
Strip Length: 7 mm (0.28 in)
-
Tightening Torque: 0.5 Nm (0.37 ft-lb)
Field Signal Limits
-
Hydrogen (Group A & B): Max Loop Inductance 6 mH, Max Loop Capacitance 0.25 µF
-
Non-Hydrogen (Group C & D): Max Loop Inductance 20 mH, Max Loop Capacitance 5 µF
Product Benefits