SR489-P5-LO-A20-E
Description
Description
Description
The SR489-P5-LO-A20-E from GE Multilin is a generator management relay designed for advanced protection functions, including overcurrent, offline conditions, and inadvertent energization. It features programmable curves, precise timing, and flexible pickup levels.
Overcurrent Alarm
-
Pickup Level: 0.10–1.50 × FLA (0.01 steps, avg phase current)
-
Time Delay: 0.1–250.0 s (0.1 s steps)
-
Pickup Accuracy: Matches phase current inputs
-
Timing Accuracy: ±100 ms or ±0.5%
Offline Overcurrent
-
Pickup Level: 0.05–1.00 × CT (0.01 steps, any phase)
-
Time Delay: 3–99 cycles (1 cycle steps)
-
Pickup Accuracy: Matches phase current inputs
-
Timing Accuracy: ±50 ms @ 50/60 Hz
Inadvertent Energization
-
Arming Signal: Based on undervoltage or breaker status
-
Pickup Level: 0.05–3.00 × CT (0.01 steps, any phase)
-
Time Delay: No intentional delay
-
Pickup Accuracy: Matches phase current inputs
-
Timing Accuracy: ±50 ms @ 50/60 Hz
Phase Overcurrent
-
Voltage Restraint: Programmable fixed characteristic
-
Pickup Level: 0.15–20.00 × CT (0.01 steps, any phase)
-
Curve Shapes: ANSI, IEC, IAC, Flexcurve, Definite Time
-
Time Delay: 0.000–100.000 s (0.001 s steps)
-
Pickup Accuracy: Matches phase current inputs
-
Timing Accuracy: ±50 ms @ 50/60 Hz or ±0.5%
Negative Sequence Overcurrent
-
Pickup Level: 3–100% FLA (1% steps)
-
Curve Shape: I²t (k-defined), definite time alarm
-
Time Delay: 0.1–100.0 s (0.1 s steps)
-
Pickup Accuracy: Matches phase current inputs
-
Timing Accuracy: ±100 ms or ±0.5%
Product Benefits
Product Benefits
- 100% genuine products in stock with fast delivery. Learn more...
- 30-day return policy for quality assurance. Learn more...
- 12-month warranty for peace of mind. Learn more...
Reviews
Reviews


Have a question?
Notified by email when this product becomes available
Recommended products
Recently viewed product
Subscribeto our emails
Be the first to know about new collections and exclusive offers.